[Code of Federal Regulations]
[Title 29, Volume 5]
[Revised as of January 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 29CFR1910.305]

[Page 854-866]
 
                             TITLE 29--LABOR
 
CHAPTER XVII--OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT 
                                OF LABOR
 
PART 1910_OCCUPATIONAL SAFETY AND HEALTH STANDARDS--Table of Contents
 
                          Subpart S_Electrical
 
Sec.  1910.305  Wiring methods, components, and equipment for general use.

    (a) Wiring methods. The provisions of this section do not apply to 
the conductors that are an integral part of factory-assembled equipment.
    (1) General requirements--(i) Electrical continuity of metal 
raceways and enclosures. Metal raceways, cable armor, and other metal 
enclosures for conductors shall be metallically joined together into a 
continuous electric conductor and shall be so connected to all boxes, 
fittings, and cabinets as to provide effective electrical continuity.
    (ii) Wiring in ducts. No wiring systems of any type shall be 
installed in ducts used to transport dust, loose stock or flammable 
vapors. No wiring system of any type may be installed in any duct used 
for vapor removal or for ventilation of commercial-type cooking 
equipment, or in any shaft containing only such ducts.
    (2) Temporary wiring. Temporary electrical power and lighting wiring 
methods may be of a class less than would be required for a permanent 
installation. Except as specifically modified in this paragraph, all 
other requirements of this subpart for permanent wiring shall apply to 
temporary wiring installations.
    (i) Uses permitted, 600 volts, nominal, or less. Temporary 
electrical power and lighting installations 600 volts, nominal, or less 
may be used only:
    (A) During and for remodeling, maintenance, repair, or demolition of 
buildings, structures, or equipment, and similar activities;
    (B) For experimental or development work, and
    (C) For a period not to exceed 90 days for Christmas decorative 
lighting, carnivals, and similar purposes.
    (ii) Uses permitted, over 600 volts, nominal. Temporary wiring over 
600 volts, nominal, may be used only during periods of tests, 
experiments, or emergencies.
    (iii) General requirements for temporary wiring. (A) Feeders shall 
originate in an approved distribution center. The conductors shall be 
run as multiconductor cord or cable assemblies, or, where not subject to 
physical damage, they may be run as open conductors on insulators not 
more than 10 feet apart.
    (B) Branch circuits shall originate in an approved power outlet or 
panelboard. Conductors shall be multiconductor cord or cable assemblies 
or open conductors. If run as open conductors they shall be fastened at 
ceiling height every 10 feet. No branch-circuit conductor may be laid on 
the floor. Each branch circuit that supplies receptacles or fixed 
equipment shall contain a separate equipment grounding conductor if run 
as open conductors.

[[Page 855]]

    (C) Receptacles shall be of the grounding type. Unless installed in 
a complete metallic raceway, each branch circuit shall contain a 
separate equipment grounding conductor and all receptacles shall be 
electrically connected to the grounding conductor.
    (D) No bare conductors nor earth returns may be used for the wiring 
of any temporary circuit.
    (E) Suitable disconnecting switches or plug connectors shall be 
installed to permit the disconnection of all ungrounded conductors of 
each temporary circuit.
    (F) Lamps for general illumination shall be protected from 
accidental contact or breakage. Protection shall be provided by 
elevation of at least 7 feet from normal working surface or by a 
suitable fixture or lampholder with a guard.
    (G) Flexible cords and cables shall be protected from accidental 
damage. Sharp corners and projections shall be avoided. Where passing 
through doorways or other pinch points, flexible cords and cables shall 
be provided with protection to avoid damage.
    (3) Cable trays--(i) Uses permitted. (a) Only the following may be 
installed in cable tray systems:
    (1) Mineral-insulated metal-sheathed cable (Type MI);
    (2) Armored cable (Type AC);
    (3) Metal-clad cable (Type MC);
    (4) Power-limited tray cable (Type PLTC);
    (5) Nonmetallic-sheathed cable (Type NM or NMC);
    (6) Shielded nonmetallic-sheathed cable (Type SNM);
    (7) Multiconductor service-entrance cable (Type SE or USE);
    (8) Multiconductor underground feeder and branch-circuit cable (Type 
UF);
    (9) Power and control tray cable (Type TC);
    (10) Other factory-assembled, multiconductor control, signal, or 
power cables which are specifically approved for installation in cable 
trays; or
    (11) Any approved conduit or raceway with its contained conductors.
    (b) In industrial establishments only, where conditions of 
maintenance and supervision assure that only qualified persons will 
service the installed cable tray system, the following cables may also 
be installed in ladder, ventilated trough, or 4 inch ventilated channel-
type cable trays:
    (1) Single conductor cables which are 250 MCM or larger and are 
Types RHH, RHW, MV, USE, or THW, and other 250 MCM or larger single 
conductor cables if specifically approved for installation in cable 
trays. Where exposed to direct rays of the sun, cables shall be 
sunlight-resistant.
    (2) Type MV cables, where exposed to direct rays of the sun, shall 
be sunlight-resistant.
    (c) Cable trays in hazardous (classified) locations shall contain 
only the cable types permitted in such locations.
    (ii) Uses not permitted. Cable tray systems may not be used in 
hoistways or where subjected to severe physical damage.
    (4) Open wiring on insulators--(i) Uses permitted. Open wiring on 
insulators is only permitted on systems of 600 volts, nominal, or less 
for industrial or agricultural establishments and for services.
    (ii) Conductor supports. Conductors shall be rigidly supported on 
noncombustible, nonabsorbent insulating materials and may not contact 
any other objects.
    (iii) Flexible nonmetallic tubing. In dry locations where not 
exposed to severe physical damage, conductors may be separately enclosed 
in flexible nonmetallic tubing. The tubing shall be in continuous 
lengths not exceeding 15 feet and secured to the surface by straps at 
intervals not exceeding 4 feet 6 inches.
    (iv) Through walls, floors, wood cross members, etc. Open conductors 
shall be separated from contact with walls, floors, wood cross members, 
or partitions through which they pass by tubes or bushings of 
noncombustible, nonabsorbent insulating material. If the bushing is 
shorter than the hole, a waterproof sleeve of nonconductive material 
shall be inserted in the hole and an insulating bushing slipped into the 
sleeve at each end in such a manner as to keep the conductors absolutely 
out of contact with the sleeve. Each conductor shall be carried through 
a separate tube or sleeve.

[[Page 856]]

    (v) Protection from physical damage. Conductors within 7 feet from 
the floor are considered exposed to physical damage. Where open 
conductors cross ceiling joints and wall studs and are exposed to 
physical damage, they shall be protected.
    (b) Cabinets, boxes, and fittings--(1) Conductors entering boxes, 
cabinets, or fittings. Conductors entering boxes, cabinets, or fittings 
shall also be protected from abrasion, and openings through which 
conductors enter shall be effectively closed. Unused openings in 
cabinets, boxes, and fittings shall be effectively closed.
    (2) Covers and canopies. All pull boxes, junction boxes, and 
fittings shall be provided with covers approved for the purpose. If 
metal covers are used they shall be grounded. In completed installations 
each outlet box shall have a cover, faceplate, or fixture canopy. Covers 
of outlet boxes having holes through which flexible cord pendants pass 
shall be provided with bushings designed for the purpose or shall have 
smooth, well-rounded surfaces on which the cords may bear.
    (3) Pull and junction boxes for systems over 600 volts, nominal. In 
addition to other requirements in this section for pull and junction 
boxes, the following shall apply to these boxes for systems over 600 
volts, nominal:
    (i) Boxes shall provide a complete enclosure for the contained 
conductors or cables.
    (ii) Boxes shall be closed by suitable covers securely fastened in 
place. Underground box covers that weigh over 100 pounds meet this 
requirement. Covers for boxes shall be permanently marked ``HIGH 
VOLTAGE.'' The marking shall be on the outside of the box cover and 
shall be readily visible and legible.
    (c) Switches--(1) Knife switches. Single-throw knife switches shall 
be so connected that the blades are dead when the switch is in the open 
position. Single-throw knife switches shall be so placed that gravity 
will not tend to close them. Single-throw knife switches approved for 
use in the inverted position shall be provided with a locking device 
that will ensure that the blades remain in the open position when so 
set. Double-throw knife switches may be mounted so that the throw will 
be either vertical or horizontal. However, if the throw is vertical a 
locking device shall be provided to ensure that the blades remain in the 
open position when so set.
    (2) Faceplates for flush-mounted snap switches. Flush snap switches 
that are mounted in ungrounded metal boxes and located within reach of 
conducting floors or other conducting surfaces shall be provided with 
faceplates of nonconducting, noncombustible material.
    (d) Switchboards and panelboards. Switchboards that have any exposed 
live parts shall be located in permanently dry locations and accessible 
only to qualified persons. Panelboards shall be mounted in cabinets, 
cutout boxes, or enclosures approved for the purpose and shall be dead 
front. However, panelboards other than the dead front externally-
operable type are permitted where accessible only to qualified persons. 
Exposed blades of knife switches shall be dead when open.
    (e) Enclosures for damp or wet locations. (1) Cabinets, cutout 
boxes, fittings, boxes, and panelboard enclosures in damp or wet 
locations shall be installed so as to prevent moisture or water from 
entering and accumulating within the enclosures. In wet locations the 
enclosures shall be weatherproof.
    (2) Switches, circuit breakers, and switchboards installed in wet 
locations shall be enclosed in weatherproof enclosures.
    (f) Conductors for general wiring. All conductors used for general 
wiring shall be insulated unless otherwise permitted in this Subpart. 
The conductor insulation shall be of a type that is approved for the 
voltage, operating temperature, and location of use. Insulated 
conductors shall be distinguishable by appropriate color or other 
suitable means as being grounded conductors, ungrounded conductors, or 
equipment grounding conductors.
    (g) Flexible cords and cables--(1) Use of flexible cords and cables. 
(i) Flexible cords and cables shall be approved and suitable for 
conditions of use and location. Flexible cords and cables shall be used 
only for:
    (A) Pendants;
    (B) Wiring of fixtures;

[[Page 857]]

    (C) Connection of portable lamps or appliances;
    (D) Elevator cables;
    (E) Wiring of cranes and hoists;
    (F) Connection of stationary equipment to facilitate their frequent 
interchange;
    (G) Prevention of the transmission of noise or vibration;
    (H) Appliances where the fastening means and mechanical connections 
are designed to permit removal for maintenance and repair; or
    (I) Data processing cables approved as a part of the data processing 
system.
    (ii) If used as permitted in paragraphs (g)(1)(i)(c), (g)(1)(i)(f), 
or (g)(1)(i)(h) of this section, the flexible cord shall be equipped 
with an attachment plug and shall be energized from an approved 
receptacle outlet.
    (iii) Unless specifically permitted in paragraph (g)(1)(i) of this 
section, flexible cords and cables may not be used:
    (A) As a substitute for the fixed wiring of a structure;
    (B) Where run through holes in walls, ceilings, or floors;
    (C) Where run through doorways, windows, or similar openings;
    (D) Where attached to building surfaces; or
    (E) Where concealed behind building walls, ceilings, or floors.
    (iv) Flexible cords used in show windows and showcases shall be Type 
S, SO, SJ, SJO, ST, STO, SJT, SJTO, or AFS except for the wiring of 
chain-supported lighting fixtures and supply cords for portable lamps 
and other merchandise being displayed or exhibited.
    (2) Identification, splices, and terminations. (i) A conductor of a 
flexible cord or cable that is used as a grounded conductor or an 
equipment grounding conductor shall be distinguishable from other 
conductors. Types SJ, SJO, SJT, SJTO, S, SO, ST, and STO shall be 
durably marked on the surface with the type designation, size, and 
number of conductors.
    (ii) Flexible cords shall be used only in continuous lengths without 
splice or tap. Hard service flexible cords No. 12 or larger may be 
repaired if spliced so that the splice retains the insulation, outer 
sheath properties, and usage characteristics of the cord being spliced.
    (iii) Flexible cords shall be connected to devices and fittings so 
that strain relief is provided which will prevent pull from being 
directly transmitted to joints or terminal screws.
    (h) Portable cables over 600 volts, nominal. Multiconductor portable 
cable for use in supplying power to portable or mobile equipment at over 
600 volts, nominal, shall consist of No. 8 or larger conductors 
employing flexible stranding. Cables operated at over 2,000 volts shall 
be shielded for the purpose of confining the voltage stresses to the 
insulation. Grounding conductors shall be provided. Connectors for these 
cables shall be of a locking type with provisions to prevent their 
opening or closing while energized. Strain relief shall be provided at 
connections and terminations. Portable cables may not be operated with 
splices unless the splices are of the permanent molded, vulcanized, or 
other approved type. Termination enclosures shall be suitably marked 
with a high voltage hazard warning, and terminations shall be accessible 
only to authorized and qualified personnel.
    (i) Fixture wires--(1) General. Fixture wires shall be approved for 
the voltage, temperature, and location of use. A fixture wire which is 
used as a grounded conductor shall be identified.
    (2) Uses permitted. Fixture wires may be used:
    (i) For installation in lighting fixtures and in similar equipment 
where enclosed or protected and not subject to bending or twisting in 
use; or
    (ii) For connecting lighting fixtures to the branch-circuit 
conductors supplying the fixtures.
    (3) Uses not permitted. Fixture wires may not be used as branch-
circuit conductors except as permitted for Class 1 power limited 
circuits.
    (j) Equipment for general use--(1) Lighting fixtures, lampholders, 
lamps, and receptacles. (i) Fixtures, lampholders, lamps, rosettes, and 
receptacles may have no live parts normally exposed to employee contact. 
However, rosettes and cleat-type lampholders and receptacles located at 
least 8 feet above the floor may have exposed parts.

[[Page 858]]

    (ii) Handlamps of the portable type supplied through flexible cords 
shall be equipped with a handle of molded composition or other material 
approved for the purpose, and a substantial guard shall be attached to 
the lampholder or the handle.
    (iii) Lampholders of the screw-shell type shall be installed for use 
as lampholders only. Lampholders installed in wet or damp locations 
shall be of the weatherproof type.
    (iv) Fixtures installed in wet or damp locations shall be approved 
for the purpose and shall be so constructed or installed that water 
cannot enter or accumulate in wireways, lampholders, or other electrical 
parts.
    (2) Receptacles, cord connectors, and attachment plugs (caps). (i) 
Receptacles, cord connectors, and attachment plugs shall be constructed 
so that no receptacle or cord connector will accept an attachment plug 
with a different voltage or current rating than that for which the 
device is intended. However, a 20-ampere T-slot receptacle or cord 
connector may accept a 15-ampere attachment plug of the same voltage 
rating.
    (ii) A receptacle installed in a wet or damp location shall be 
suitable for the location.
    (3) Appliances. (i) Appliances, other than those in which the 
current-carrying parts at high temperatures are necessarily exposed, may 
have no live parts normally exposed to employee contact.
    (ii) A means shall be provided to disconnect each appliance.
    (iii) Each appliance shall be marked with its rating in volts and 
amperes or volts and watts.
    (4) Motors. This paragraph applies to motors, motor circuits, and 
controllers.
    (i) In sight from. If specified that one piece of equipment shall be 
``in sight from'' another piece of equipment, one shall be visible and 
not more than 50 feet from the other.
    (ii) Disconnecting means. (A) A disconnecting means shall be located 
in sight from the controller location. However, a single disconnecting 
means may be located adjacent to a group of coordinated controllers 
mounted adjacent to each other on a multi-motor continuous process 
machine. The controller disconnecting means for motor branch circuits 
over 600 volts, nominal, may be out of sight of the controller, if the 
controller is marked with a warning label giving the location and 
identification of the disconnecting means which is to be locked in the 
open position.
    (B) The disconnecting means shall disconnect the motor and the 
controller from all ungrounded supply conductors and shall be so 
designed that no pole can be operated independently.
    (C) If a motor and the driven machinery are not in sight from the 
controller location, the installation shall comply with one of the 
following conditions:
    (1) The controller disconnecting means shall be capable of being 
locked in the open position.
    (2) A manually operable switch that will disconnect the motor from 
its source of supply shall be placed in sight from the motor location.
    (D) The disconnecting means shall plainly indicate whether it is in 
the open (off) or closed (on) position.
    (E) The disconnecting means shall be readily accessible. If more 
than one disconnect is provided for the same equipment, only one need be 
readily accessible.
    (F) An individual disconnecting means shall be provided for each 
motor, but a single disconnecting means may be used for a group of 
motors under any one of the following conditions:
    (1) If a number of motors drive special parts of a single machine or 
piece of apparatus, such as a metal or woodworking machine, crane, or 
hoist;
    (2) If a group of motors is under the protection of one set of 
branch-circuit protective devices; or
    (3) If a group of motors is in a single room in sight from the 
location of the disconnecting means.
    (iii) Motor overload, short-circuit, and ground-fault protection. 
Motors, motor-control apparatus, and motor branch-circuit conductors 
shall be protected against overheating due to motor overloads or failure 
to start, and against short-circuits or ground faults. These provisions 
shall not require overload protection that will stop a motor

[[Page 859]]

where a shutdown is likely to introduce additional or increased hazards, 
as in the case of fire pumps, or where continued operation of a motor is 
necessary for a safe shutdown of equipment or process and motor overload 
sensing devices are connected to a supervised alarm.
    (iv) Protection of live parts--all voltages. (A) Stationary motors 
having commutators, collectors, and brush rigging located inside of 
motor end brackets and not conductively connected to supply circuits 
operating at more than 150 volts to ground need not have such parts 
guarded. Exposed live parts of motors and controllers operating at 50 
volts or more between terminals shall be guarded against accidental 
contact by any of the following:
    (1) By installation in a room or enclosure that is accessible only 
to qualified persons;
    (2) By installation on a suitable balcony, gallery, or platform, so 
elevated and arranged as to exclude unqualified persons; or
    (3) By elevation 8 feet or more above the floor.
    (B) Where live parts of motors or controllers operating at over 150 
volts to ground are guarded against accidental contact only by location, 
and where adjustment or other attendance may be necessary during the 
operation of the apparatus, suitable insulating mats or platforms shall 
be provided so that the attendant cannot readily touch live parts unless 
standing on the mats or platforms.
    (5) Transformers. (i) The following paragraphs cover the 
installation of all transformers except the following:
    (A) Current transformers;
    (B) Dry-type transformers installed as a component part of other 
apparatus;
    (C) Transformers which are an integral part of an X-ray, high 
frequency, or electrostatic-coating apparatus;
    (D) Transformers used with Class 2 and Class 3 circuits, sign and 
outline lighting, electric discharge lighting, and power-limited fire-
protective signalling circuits; and
    (E) Liquid-filled or dry-type transformers used for research, 
development, or testing, where effective safeguard arrangements are 
provided.
    (ii) The operating voltage of exposed live parts of transformer 
installations shall be indicated by warning signs or visible markings on 
the equipment or structure.
    (iii) Dry-type, high fire point liquid-insulated, and askarel-
insulated transformers installed indoors and rated over 35kV shall be in 
a vault.
    (iv) If they present a fire hazard to employees, oil-insulated 
transformers installed indoors shall be in a vault.
    (v) Combustible material, combustible buildings and parts of 
buildings, fire escapes, and door and window openings shall be 
safeguarded from fires which may originate in oil-insulated transformers 
attached to or adjacent to a building or combustible material.
    (vi) Transformer vaults shall be constructed so as to contain fire 
and combustible liquids within the vault and to prevent unauthorized 
access. Locks and latches shall be so arranged that a vault door can be 
readily opened from the inside.
    (vii) Any pipe or duct system foreign to the vault installation may 
not enter or pass through a transformer vault.
    (viii) Materials may not be stored in transformer vaults.
    (6) Capacitors. (i) All capacitors, except surge capacitors or 
capacitors included as a component part of other apparatus, shall be 
provided with an automatic means of draining the stored charge after the 
capacitor is disconnected from its source of supply.
    (ii) Capacitors rated over 600 volts, nominal, shall comply with the 
following additional requirements:
    (A) Isolating or disconnecting switches (with no interrupting 
rating) shall be interlocked with the load interrupting device or shall 
be provided with prominently displayed caution signs to prevent 
switching load current.
    (B) For series capacitors (see Sec.  1910.302(b)(3)), the proper 
switching shall be assured by use of at least one of the following:
    (1) Mechanically sequenced isolating and bypass switches,
    (2) Interlocks, or
    (3) Switching procedure prominently displayed at the switching 
location.

[[Page 860]]

    (7) Storage batteries. Provisions shall be made for sufficient 
diffusion and ventilation of gases from storage batteries to prevent the 
accumulation of explosive mixtures.

[46 FR 4056, Jan. 16, 1981; 46 FR 40185, Aug. 7, 1981]

    Effective Date Note: At 72 FR 7201, Feb. 14, 2007, Sec.  1910.305 
was revised, effective Aug. 13, 2007. For the convenience of the user, 
the revised text is set forth as follows:

Sec.  1910.305  Wiring methods, components, and equipment for general 
          use.

    (a) Wiring methods. The provisions of this section do not apply to 
conductors that are an integral part of factory-assembled equipment.
    (1) General requirements. (i) Metal raceways, cable trays, cable 
armor, cable sheath, enclosures, frames, fittings, and other metal 
noncurrent-carrying parts that are to serve as grounding conductors, 
with or without the use of supplementary equipment grounding conductors, 
shall be effectively bonded where necessary to ensure electrical 
continuity and the capacity to conduct safely any fault current likely 
to be imposed on them. Any nonconductive paint, enamel, or similar 
coating shall be removed at threads, contact points, and contact 
surfaces or be connected by means of fittings designed so as to make 
such removal unnecessary.
    (ii) Where necessary for the reduction of electrical noise 
(electromagnetic interference) of the grounding circuit, an equipment 
enclosure supplied by a branch circuit may be isolated from a raceway 
containing circuits supplying only that equipment by one or more listed 
nonmetallic raceway fittings located at the point of attachment of the 
raceway to the equipment enclosure. The metal raceway shall be 
supplemented by an internal insulated equipment grounding conductor 
installed to ground the equipment enclosure.
    (iii) No wiring systems of any type may be installed in ducts used 
to transport dust, loose stock, or flammable vapors. No wiring system of 
any type may be installed in any duct used for vapor removal or for 
ventilation of commercial-type cooking equipment, or in any shaft 
containing only such ducts.
    (2) Temporary wiring. Except as specifically modified in this 
paragraph, all other requirements of this subpart for permanent wiring 
shall also apply to temporary wiring installations.
    (i) Temporary electrical power and lighting installations of 600 
volts, nominal, or less may be used only as follows:
    (A) During and for remodeling, maintenance, or repair of buildings, 
structures, or equipment, and similar activities;
    (B) For a period not to exceed 90 days for Christmas decorative 
lighting, carnivals, and similar purposes; or
    (C) For experimental or development work, and during emergencies.
    (ii) Temporary wiring shall be removed immediately upon completion 
of the project or purpose for which the wiring was installed.
    (iii) Temporary electrical installations of more than 600 volts may 
be used only during periods of tests, experiments, emergencies, or 
construction-like activities.
    (iv) The following requirements apply to feeders:
    (A) Feeders shall originate in an approved distribution center.
    (B) Conductors shall be run as multiconductor cord or cable 
assemblies. However, if installed as permitted in paragraph (a)(2)(i)(C) 
of this section, and if accessible only to qualified persons, feeders 
may be run as single insulated conductors.
    (v) The following requirements apply to branch circuits:
    (A) Branch circuits shall originate in an approved power outlet or 
panelboard.
    (B) Conductors shall be multiconductor cord or cable assemblies or 
open conductors. If run as open conductors, they shall be fastened at 
ceiling height every 3.05 m (10.0 ft).
    (C) No branch-circuit conductor may be laid on the floor.
    (D) Each branch circuit that supplies receptacles or fixed equipment 
shall contain a separate equipment grounding conductor if run as open 
conductors.
    (vi) Receptacles shall be of the grounding type. Unless installed in 
a continuous grounded metallic raceway or metallic covered cable, each 
branch circuit shall contain a separate equipment grounding conductor 
and all receptacles shall be electrically connected to the grounding 
conductor.
    (vii) No bare conductors nor earth returns may be used for the 
wiring of any temporary circuit.
    (viii) Suitable disconnecting switches or plug connectors shall be 
installed to permit the disconnection of all ungrounded conductors of 
each temporary circuit. Multiwire branch circuits shall be provided with 
a means to disconnect simultaneously all ungrounded conductors at the 
power outlet or panelboard where the branch circuit originated.

    Note to paragraph (a)(2)(viii) of this section. Circuit breakers 
with their handles connected by approved handle ties are considered a 
single disconnecting means for the purpose of this requirement.

    (ix) All lamps for general illumination shall be protected from 
accidental contact or breakage by a suitable fixture or lampholder with 
a guard. Brass shell, paper-lined sockets, or other metal-cased sockets 
may not be used unless the shell is grounded.

[[Page 861]]

    (x) Flexible cords and cables shall be protected from accidental 
damage, as might be caused, for example, by sharp corners, projections, 
and doorways or other pinch points.
    (xi) Cable assemblies and flexible cords and cables shall be 
supported in place at intervals that ensure that they will be protected 
from physical damage. Support shall be in the form of staples, cables 
ties, straps, or similar type fittings installed so as not to cause 
damage.
    (3) Cable trays. (i) Only the following wiring methods may be 
installed in cable tray systems: armored cable; electrical metallic 
tubing; electrical nonmetallic tubing; fire alarm cables; flexible metal 
conduit; flexible metallic tubing; instrumentation tray cable; 
intermediate metal conduit; liquidtight flexible metal conduit; 
liquidtight flexible nonmetallic conduit; metal-clad cable; mineral-
insulated, metal-sheathed cable; multiconductor service-entrance cable; 
multiconductor underground feeder and branch-circuit cable; multipurpose 
and communications cables; nonmetallic-sheathed cable; power and control 
tray cable; power-limited tray cable; optical fiber cables; and other 
factory-assembled, multiconductor control, signal, or power cables that 
are specifically approved for installation in cable trays, rigid metal 
conduit, and rigid nonmetallic conduit.
    (ii) In industrial establishments where conditions of maintenance 
and supervision assure that only qualified persons will service the 
installed cable tray system, the following cables may also be installed 
in ladder, ventilated-trough, or ventilated-channel cable trays:
    (A) Single conductor cable; the cable shall be No. 1/0 or larger and 
shall be of a type listed and marked on the surface for use in cable 
trays; where Nos. 1/0 through 4/0 single conductor cables are installed 
in ladder cable tray, the maximum allowable rung spacing for the ladder 
cable tray shall be 229 mm (9 in.); where exposed to direct rays of the 
sun, cables shall be identified as being sunlight resistant;
    (B) Welding cables installed in dedicated cable trays;
    (C) Single conductors used as equipment grounding conductors; these 
conductors, which may be insulated, covered, or bare, shall be No. 4 or 
larger; and
    (D) Multiconductor cable, Type MV; where exposed to direct rays of 
the sun, the cable shall be identified as being sunlight resistant.
    (iii) Metallic cable trays may be used as equipment grounding 
conductors only where continuous maintenance and supervision ensure that 
qualified persons will service the installed cable tray system.
    (iv) Cable trays in hazardous (classified) locations may contain 
only the cable types permitted in such locations. (See Sec.  1910.307.)
    (v) Cable tray systems may not be used in hoistways or where 
subjected to severe physical damage.
    (4) Open wiring on insulators. (i) Open wiring on insulators is only 
permitted on systems of 600 volts, nominal, or less for industrial or 
agricultural establishments, indoors or outdoors, in wet or dry 
locations, where subject to corrosive vapors, and for services.
    (ii) Conductors smaller than No. 8 shall be rigidly supported on 
noncombustible, nonabsorbent insulating materials and may not contact 
any other objects. Supports shall be installed as follows:
    (A) Within 152 mm (6 in.) from a tap or splice;
    (B) Within 305 mm (12 in.) of a dead-end connection to a lampholder 
or receptacle; and
    (C) At intervals not exceeding 1.37 m (4.5 ft), and at closer 
intervals sufficient to provide adequate support where likely to be 
disturbed.
    (iii) In dry locations, where not exposed to severe physical damage, 
conductors may be separately enclosed in flexible nonmetallic tubing. 
The tubing shall be in continuous lengths not exceeding 4.57 m (15.0 ft) 
and secured to the surface by straps at intervals not exceeding 1.37 m 
(4.5 ft).
    (iv) Open conductors shall be separated from contact with walls, 
floors, wood cross members, or partitions through which they pass by 
tubes or bushings of noncombustible, nonabsorbent insulating material. 
If the bushing is shorter than the hole, a waterproof sleeve of 
nonconductive material shall be inserted in the hole and an insulating 
bushing slipped into the sleeve at each end in such a manner as to keep 
the conductors absolutely out of contact with the sleeve. Each conductor 
shall be carried through a separate tube or sleeve.
    (v) Where open conductors cross ceiling joints and wall studs and 
are exposed to physical damage (for example, located within 2.13 m (7.0 
ft) of the floor), they shall be protected.
    (b) Cabinets, boxes, and fittings--(1) Conductors entering boxes, 
cabinets, or fittings. (i) Conductors entering cutout boxes, cabinets, 
or fittings shall be protected from abrasion, and openings through which 
conductors enter shall be effectively closed.
    (ii) Unused openings in cabinets, boxes, and fittings shall be 
effectively closed.
    (iii) Where cable is used, each cable shall be secured to the 
cabinet, cutout box, or meter socket enclosure. However, where cable 
with an entirely nonmetallic sheath enters the top of a surface-mounted 
enclosure through one or more nonflexible raceways not less than 457 mm 
(18 in.) or more than 3.05 m (10.0 ft) in length, the cable need not be 
secured to the cabinet, box, or enclosure provided all of the following 
conditions are met:

[[Page 862]]

    (A) Each cable is fastened within 305 mm (12 in.) of the outer end 
of the raceway, measured along the sheath;
    (B) The raceway extends directly above the enclosure and does not 
penetrate a structural ceiling;
    (C) A fitting is provided on each end of the raceway to protect the 
cable from abrasion, and the fittings remain accessible after 
installation;
    (D) The raceway is sealed or plugged at the outer end using approved 
means so as to prevent access to the enclosure through the raceway;
    (E) The cable sheath is continuous through the raceway and extends 
into the enclosure not less than 6.35 mm (0.25 in.) beyond the fitting;
    (F) The raceway is fastened at its outer end and at other points as 
necessary; and
    (G) Where installed as conduit or tubing, the allowable cable fill 
does not exceed that permitted for complete conduit or tubing systems.
    (2) Covers and canopies. (i) All pull boxes, junction boxes, and 
fittings shall be provided with covers identified for the purpose. If 
metal covers are used, they shall be grounded. In completed 
installations, each outlet box shall have a cover, faceplate, or fixture 
canopy. Covers of outlet boxes having holes through which flexible cord 
pendants pass shall be provided with bushings designed for the purpose 
or shall have smooth, well-rounded surfaces on which the cords may bear.
    (ii) Where a fixture canopy or pan is used, any combustible wall or 
ceiling finish exposed between the edge of the canopy or pan and the 
outlet box shall be covered with noncombustible material.
    (3) Pull and junction boxes for systems over 600 volts, nominal. In 
addition to other requirements in this section, the following 
requirements apply to pull and junction boxes for systems over 600 
volts, nominal:
    (i) Boxes shall provide a complete enclosure for the contained 
conductors or cables.
    (ii) Boxes shall be closed by suitable covers securely fastened in 
place.

    Note to paragraph (b)(3)(ii) of this section: Underground box covers 
that weigh over 45.4 kg (100 lbs) meet this requirement.

    (iii) Covers for boxes shall be permanently marked ``HIGH VOLTAGE.'' 
The marking shall be on the outside of the box cover and shall be 
readily visible and legible.
    (c) Switches--(1) Single-throw knife switches. Single-throw knife 
switches shall be so placed that gravity will not tend to close them. 
Single-throw knife switches approved for use in the inverted position 
shall be provided with a locking device that will ensure that the blades 
remain in the open position when so set.
    (2) Double-throw knife switches. Double-throw knife switches may be 
mounted so that the throw will be either vertical or horizontal. 
However, if the throw is vertical, a locking device shall be provided to 
ensure that the blades remain in the open position when so set.
    (3) Connection of switches. (i) Single-throw knife switches and 
switches with butt contacts shall be connected so that the blades are 
deenergized when the switch is in the open position.
    (ii) Single-throw knife switches, molded-case switches, switches 
with butt contacts, and circuit breakers used as switches shall be 
connected so that the terminals supplying the load are deenergized when 
the switch is in the open position. However, blades and terminals 
supplying the load of a switch may be energized when the switch is in 
the open position where the switch is connected to circuits or equipment 
inherently capable of providing a backfeed source of power. For such 
installations, a permanent sign shall be installed on the switch 
enclosure or immediately adjacent to open switches that read, 
``WARNING--LOAD SIDE TERMINALS MAY BE ENERGIZED BY BACKFEED.''
    (4) Faceplates for flush-mounted snap switches. Snap switches 
mounted in boxes shall have faceplates installed so as to completely 
cover the opening and seat against the finished surface.
    (5) Grounding. Snap switches, including dimmer switches, shall be 
effectively grounded and shall provide a means to ground metal 
faceplates, whether or not a metal faceplate is installed. However, if 
no grounding means exists within the snap-switch enclosure, or where the 
wiring method does not include or provide an equipment ground, a snap 
switch without a grounding connection is permitted for replacement 
purposes only. Such snap switches shall be provided with a faceplate of 
nonconducting, noncombustible material if they are located within reach 
of conducting floors or other conducting surfaces.
    (d) Switchboards and panelboards--(1) Switchboards with exposed live 
parts. Switchboards that have any exposed live parts shall be located in 
permanently dry locations and shall be accessible only to qualified 
persons.
    (2) Panelboard enclosures. Panelboards shall be mounted in cabinets, 
cutout boxes, or enclosures designed for the purpose and shall be dead 
front. However, panelboards other than the dead front externally-
operable type are permitted where accessible only to qualified persons.
    (3) Knife switches mounted in switchboards or panelboards. Exposed 
blades of knife switches mounted in switchboards or panelboards shall be 
dead when open.
    (e) Enclosures for damp or wet locations--(1) Cabinets, cutout 
boxes, fittings, boxes, and panelboard enclosures. Cabinets, cutout 
boxes,

[[Page 863]]

fittings, boxes, and panelboard enclosures in damp or wet locations 
shall be installed so as to prevent moisture or water from entering and 
accumulating within the enclosures and shall be mounted so there is at 
least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or 
other supporting surface. However, nonmetallic enclosures may be 
installed without the airspace on a concrete, masonry, tile, or similar 
surface. The enclosures shall be weatherproof in wet locations.
    (2) Switches, circuit breakers, and switchboards. Switches, circuit 
breakers, and switchboards installed in wet locations shall be enclosed 
in weatherproof enclosures.
    (f) Conductors for general wiring--(1) Insulation. All conductors 
used for general wiring shall be insulated unless otherwise permitted in 
this subpart.
    (2) Type. The conductor insulation shall be of a type that is 
approved for the voltage, operating temperature, and location of use.
    (3) Distinguishable. Insulated conductors shall be distinguishable 
by appropriate color or other suitable means as being grounded 
conductors, ungrounded conductors, or equipment grounding conductors.
    (g) Flexible cords and cables--(1)Use of flexible cords and cables. 
(i) Flexible cords and cables shall be approved for conditions of use 
and location.
    (ii) Flexible cords and cables may be used only for:
    (A) Pendants;
    (B) Wiring of fixtures;
    (C) Connection of portable lamps or appliances;
    (D) Portable and mobile signs;
    (E) Elevator cables;
    (F) Wiring of cranes and hoists;
    (G) Connection of stationary equipment to facilitate their frequent 
interchange;
    (H) Prevention of the transmission of noise or vibration;
    (I) Appliances where the fastening means and mechanical connections 
are designed to permit removal for maintenance and repair;
    (J) Data processing cables approved as a part of the data processing 
system;
    (K) Connection of moving parts; and
    (L) Temporary wiring as permitted in paragraph (a)(2) of this 
section.
    (iii) If used as permitted in paragraphs (g)(1)(ii)(C), 
(g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cord shall 
be equipped with an attachment plug and shall be energized from an 
approved receptacle outlet.
    (iv) Unless specifically permitted otherwise in paragraph (g)(1)(ii) 
of this section, flexible cords and cables may not be used:
    (A) As a substitute for the fixed wiring of a structure;
    (B) Where run through holes in walls, ceilings, or floors;
    (C) Where run through doorways, windows, or similar openings;
    (D) Where attached to building surfaces;
    (E) Where concealed behind building walls, ceilings, or floors; or
    (F) Where installed in raceways, except as otherwise permitted in 
this subpart.
    (v) Flexible cords used in show windows and showcases shall be Type 
S, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, SJO, SJOO, SJT, SJTO, SJTOO, SO, 
SOO, ST, STO, or STOO, except for the wiring of chain-supported lighting 
fixtures and supply cords for portable lamps and other merchandise being 
displayed or exhibited.
    (2) Identification, splices, and terminations. (i) A conductor of a 
flexible cord or cable that is used as a grounded conductor or an 
equipment grounding conductor shall be distinguishable from other 
conductors. Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, SJE, SJEO, SJEOO, 
SJO, SJT, SJTO, SJTOO, SO, SOO, ST, STO, and STOO flexible cords and 
Types G, G-GC, PPE, and W flexible cables shall be durably marked on the 
surface at intervals not exceeding 610 mm (24 in.) with the type 
designation, size, and number of conductors.
    (ii) Flexible cords may be used only in continuous lengths without 
splice or tap. Hard-service cord and junior hard-service cord No. 14 and 
larger may be repaired if spliced so that the splice retains the 
insulation, outer sheath properties, and usage characteristics of the 
cord being spliced.
    (iii) Flexible cords and cables shall be connected to devices and 
fittings so that strain relief is provided that will prevent pull from 
being directly transmitted to joints or terminal screws.
    (h) Portable cables over 600 volts, nominal. This paragraph applies 
to portable cables used at more than 600 volts, nominal.
    (1) Conductor construction. Multiconductor portable cable for use in 
supplying power to portable or mobile equipment at over 600 volts, 
nominal, shall consist of No. 8 or larger conductors employing flexible 
stranding. However, the minimum size of the insulated ground-check 
conductor of Type G-GC cables shall be No. 10.
    (2) Shielding. Cables operated at over 2,000 volts shall be shielded 
for the purpose of confining the voltage stresses to the insulation.
    (3) Equipment grounding conductors. Grounding conductors shall be 
provided.
    (4) Grounding shields. All shields shall be grounded.
    (5) Minimum bending radii. The minimum bending radii for portable 
cables during installation and handling in service shall be adequate to 
prevent damage to the cable.
    (6) Fittings. Connectors used to connect lengths of cable in a run 
shall be of a type that lock firmly together. Provisions shall be made 
to prevent opening or closing these connectors while energized. Strain 
relief shall be provided at connections and terminations.

[[Page 864]]

    (7) Splices. Portable cables may not be operated with splices unless 
the splices are of the permanent molded, vulcanized, or other approved 
type.
    (8) Terminations. Termination enclosures shall be suitably marked 
with a high voltage hazard warning, and terminations shall be accessible 
only to authorized and qualified employees.
    (i) Fixture wires--(1) General. Fixture wires shall be approved for 
the voltage, temperature, and location of use. A fixture wire which is 
used as a grounded conductor shall be identified.
    (2) Uses permitted. Fixture wires may be used only:
    (i) For installation in lighting fixtures and in similar equipment 
where enclosed or protected and not subject to bending or twisting in 
use; or
    (ii) For connecting lighting fixtures to the branch-circuit 
conductors supplying the fixtures.
    (3) Uses not permitted. Fixture wires may not be used as branch-
circuit conductors except as permitted for Class 1 power limited 
circuits and for fire alarm circuits.
    (j) Equipment for general use--(1) Lighting fixtures, lampholders, 
lamps, and receptacles. (i) Fixtures, lampholders, lamps, rosettes, and 
receptacles may have no live parts normally exposed to employee contact. 
However, rosettes and cleat-type lampholders and receptacles located at 
least 2.44 m (8.0 ft) above the floor may have exposed terminals.
    (ii) Handlamps of the portable type supplied through flexible cords 
shall be equipped with a handle of molded composition or other material 
identified for the purpose, and a substantial guard shall be attached to 
the lampholder or the handle. Metal shell, paper-lined lampholders may 
not be used.
    (iii) Lampholders of the screw-shell type shall be installed for use 
as lampholders only. Where supplied by a circuit having a grounded 
conductor, the grounded conductor shall be connected to the screw shell. 
Lampholders installed in wet or damp locations shall be of the 
weatherproof type.
    (iv) Fixtures installed in wet or damp locations shall be identified 
for the purpose and shall be so constructed or installed that water 
cannot enter or accumulate in wireways, lampholders, or other electrical 
parts.
    (2) Receptacles, cord connectors, and attachment plugs (caps). (i) 
All 15- and 20-ampere attachment plugs and connectors shall be 
constructed so that there are no exposed current-carrying parts except 
the prongs, blades, or pins. The cover for wire terminations shall be a 
part that is essential for the operation of an attachment plug or 
connector (dead-front construction). Attachment plugs shall be installed 
so that their prongs, blades, or pins are not energized unless inserted 
into an energized receptacle. No receptacles may be installed so as to 
require an energized attachment plug as its source of supply.
    (ii) Receptacles, cord connectors, and attachment plugs shall be 
constructed so that no receptacle or cord connector will accept an 
attachment plug with a different voltage or current rating than that for 
which the device is intended. However, a 20-ampere T-slot receptacle or 
cord connector may accept a 15-ampere attachment plug of the same 
voltage rating.
    (iii) Nongrounding-type receptacles and connectors may not be used 
for grounding-type attachment plugs.
    (iv) A receptacle installed in a wet or damp location shall be 
suitable for the location.
    (v) A receptacle installed outdoors in a location protected from the 
weather or in other damp locations shall have an enclosure for the 
receptacle that is weatherproof when the receptacle is covered 
(attachment plug cap not inserted and receptacle covers closed).
    Note to paragraph (j)(2)(v) of this section. A receptacle is 
considered to be in a location protected from the weather when it is 
located under roofed open porches, canopies, marquees, or the like and 
where it will not be subjected to a beating rain or water runoff.
    (vi) A receptacle installed in a wet location where the product 
intended to be plugged into it is not attended while in use (for 
example, sprinkler system controllers, landscape lighting, and holiday 
lights) shall have an enclosure that is weatherproof with the attachment 
plug cap inserted or removed.
    (vii) A receptacle installed in a wet location where the product 
intended to be plugged into it will be attended while in use (for 
example, portable tools) shall have an enclosure that is weatherproof 
when the attachment plug cap is removed.
    (3) Appliances. (i) Appliances may have no live parts normally 
exposed to contact other than parts functioning as open-resistance 
heating elements, such as the heating elements of a toaster, which are 
necessarily exposed.
    (ii) Each appliance shall have a means to disconnect it from all 
ungrounded conductors. If an appliance is supplied by more than one 
source, the disconnecting means shall be grouped and identified.
    (iii) Each electric appliance shall be provided with a nameplate 
giving the identifying name and the rating in volts and amperes, or in 
volts and watts. If the appliance is to be used on a specific frequency 
or frequencies, it shall be so marked. Where motor overload protection 
external to the appliance is required, the appliance shall be so marked.
    (iv) Marking shall be located so as to be visible or easily 
accessible after installation.

[[Page 865]]

    (4) Motors. This paragraph applies to motors, motor circuits, and 
controllers.
    (i) If specified in paragraph (j)(4) of this section that one piece 
of equipment shall be ``within sight of'' another piece of equipment, 
the piece of equipment shall be visible and not more than 15.24 m (50.0 
ft) from the other.
    (ii) An individual disconnecting means shall be provided for each 
controller. A disconnecting means shall be located within sight of the 
controller location. However, a single disconnecting means may be 
located adjacent to a group of coordinated controllers mounted adjacent 
to each other on a multi-motor continuous process machine. The 
controller disconnecting means for motor branch circuits over 600 volts, 
nominal, may be out of sight of the controller, if the controller is 
marked with a warning label giving the location and identification of 
the disconnecting means that is to be locked in the open position.
    (iii) The disconnecting means shall disconnect the motor and the 
controller from all ungrounded supply conductors and shall be so 
designed that no pole can be operated independently.
    (iv) The disconnecting means shall plainly indicate whether it is in 
the open (off) or closed (on) position.
    (v) The disconnecting means shall be readily accessible. If more 
than one disconnect is provided for the same equipment, only one need be 
readily accessible.
    (vi) An individual disconnecting means shall be provided for each 
motor, but a single disconnecting means may be used for a group of 
motors under any one of the following conditions:
    (A) If a number of motors drive several parts of a single machine or 
piece of apparatus, such as a metal or woodworking machine, crane, or 
hoist;
    (B) If a group of motors is under the protection of one set of 
branch-circuit protective devices; or
    (C) If a group of motors is in a single room within sight of the 
location of the disconnecting means.
    (vii) Motors, motor-control apparatus, and motor branch-circuit 
conductors shall be protected against overheating due to motor overloads 
or failure to start, and against short-circuits or ground faults. These 
provisions do not require overload protection that will stop a motor 
where a shutdown is likely to introduce additional or increased hazards, 
as in the case of fire pumps, or where continued operation of a motor is 
necessary for a safe shutdown of equipment or process and motor overload 
sensing devices are connected to a supervised alarm.
    (viii) Where live parts of motors or controllers operating at over 
150 volts to ground are guarded against accidental contact only by 
location, and where adjustment or other attendance may be necessary 
during the operation of the apparatus, suitable insulating mats or 
platforms shall be provided so that the attendant cannot readily touch 
live parts unless standing on the mats or platforms.
    (5) Transformers. (i) Paragraph (j)(5) of this section covers the 
installation of all transformers except the following:
    (A) Current transformers;
    (B) Dry-type transformers installed as a component part of other 
apparatus;
    (C) Transformers that are an integral part of an X-ray, high 
frequency, or electrostatic-coating apparatus;
    (D) Transformers used with Class 2 and Class 3 circuits, sign and 
outline lighting, electric discharge lighting, and power-limited fire-
alarm circuits; and
    (E) Liquid-filled or dry-type transformers used for research, 
development, or testing, where effective safeguard arrangements are 
provided.
    (ii) The operating voltage of exposed live parts of transformer 
installations shall be indicated by signs or visible markings on the 
equipment or structure.
    (iii) Dry-type, high fire point liquid-insulated, and askarel-
insulated transformers installed indoors and rated over 35kV shall be in 
a vault.
    (iv) Oil-insulated transformers installed indoors shall be installed 
in a vault.
    (v) Combustible material, combustible buildings and parts of 
buildings, fire escapes, and door and window openings shall be 
safeguarded from fires that may originate in oil-insulated transformers 
attached to or adjacent to a building or combustible material.
    (vi) Transformer vaults shall be constructed so as to contain fire 
and combustible liquids within the vault and to prevent unauthorized 
access. Locks and latches shall be so arranged that a vault door can be 
readily opened from the inside.
    (vii) Any pipe or duct system foreign to the electrical installation 
may not enter or pass through a transformer vault.
    Note to paragraph (j)(5)(vii) of this section. Piping or other 
facilities provided for vault fire protection, or for transformer 
cooling, are not considered foreign to the electrical installation.
    (viii) Material may not be stored in transformer vaults.
    (6) Capacitors. (i) All capacitors, except surge capacitors or 
capacitors included as a component part of other apparatus, shall be 
provided with an automatic means of draining the stored charge after the 
capacitor is disconnected from its source of supply.
    (ii) The following requirements apply to capacitors installed on 
circuits operating at more than 600 volts, nominal:
    (A) Group-operated switches shall be used for capacitor switching 
and shall be capable of the following:

[[Page 866]]

    (1) Carrying continuously not less than 135 percent of the rated 
current of the capacitor installation;
    (2) Interrupting the maximum continuous load current of each 
capacitor, capacitor bank, or capacitor installation that will be 
switched as a unit;
    (3) Withstanding the maximum inrush current, including contributions 
from adjacent capacitor installations; and
    (4) Carrying currents due to faults on the capacitor side of the 
switch;
    (B) A means shall be installed to isolate from all sources of 
voltage each capacitor, capacitor bank, or capacitor installation that 
will be removed from service as a unit. The isolating means shall 
provide a visible gap in the electric circuit adequate for the operating 
voltage;
    (C) Isolating or disconnecting switches (with no interrupting 
rating) shall be interlocked with the load interrupting device or shall 
be provided with prominently displayed caution signs to prevent 
switching load current; and
    (D) For series capacitors, the proper switching shall be assured by 
use of at least one of the following:
    (1) Mechanically sequenced isolating and bypass switches;
    (2) Interlocks; or
    (3) Switching procedure prominently displayed at the switching 
location.
    (7) Storage Batteries. Provisions shall be made for sufficient 
diffusion and ventilation of gases from storage batteries to prevent the 
accumulation of explosive mixtures.