Table 6.2 - Fishing Piers and Platforms Alternatives Item: Gangways - Maximum Slope Proposed Guidelines: Exception permits gangways to exceed 1:12 maximum slope based on distance between design high point and level of water, and square footage of fixed and floating piers. Final Guidelines: Exception permits gangways to exceed 1:12 maximum slope where total length of gangways serving as part of accessible route is at least 30 feet. Item: Gangways - Alterations Proposed Guidelines: No exception. Final Guidelines: Where existing gangways are replaced or altered, gangways are not required to be lengthened unless triggered by alterations to primary function areas. Item: LULAs and Platform Lifts Proposed Guidelines: No exception. Final Guidelines: Limited use/limited application elevators (LULAs) and platform lifts permitted in lieu of gangways. Item: Railings - Edge Protection Proposed Guidelines: No exception. Final Guidelines: Where railing is 34 inches or less above ground or deck surface, edge protection is not required if deck surface extends 12 inches minimum beyond inside face of railing. Toe clearance must be 9 inches minimum above ground or deck surface beyond railing. Toe clearance must be 30 inches minimum wide. Item: Railings - Height Proposed Guidelines: At least 25% of railings required to be 32 inches maximum above ground or deck surface. Final Guidelines: At least 25% of railings required to be 34 inches maximum above ground or deck surface. Item: Guard Complying with IBC Proposed Guidelines: No exception. Final Guidelines: Maximum height requirement does not apply to portion of fishing pier or platform where guard complying with sections 1003.2.12.1 (Height) and 1003.2.12.2 (Openings) of International Building Code (IBC) provided.