USACE / NAVFAC / AFCESA / NASA UFGS-08550 (August 2001)
------------------------------
Preparing Activity:
NAVFACMasterFormatTM 2004 - 08 52 00
Superseding
UFGS-08550 (September 1999)
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated 23 June 2005
Latest change indicated by CHG tags
Section Table of Contents
SECTION 08550
WOOD WINDOWS
08/01
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY AND STORAGE
PART 2 PRODUCTS
2.1 WOOD WINDOWS
2.1.1 Single-Hung and Double-Hung Windows
2.1.2 Awning Windows (Top Hinged)
2.1.3 Casement Windows
2.1.4 Horizontal-Sliding Windows
2.1.5 Stationary Windows
2.2 FINISHES
2.2.1 Paint
2.2.2 Vinyl (PVC) Cladding
2.2.3 Aluminum Cladding
2.2.3.1 Aluminum Finish
2.2.3.2 Anodic Coating
2.2.3.3 Organic Coating
2.3 INSECT SCREENS
2.4 STORM SASH
2.4.1 Finishes
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Wood and Wood Clad Windows
3.1.2 Insect Screen
3.1.3 Storm Windows
3.2 ADJUSTMENTS
3.3 CLEANING
SECTION 08550
WOOD WINDOWS
NOTE: This guide specification covers the requirements for
wood windows of
the following types: single-hung, double-hung, awning, casement, horizontal
sliding, and non-operative (stationary window unit).
Comments and suggestions on this guide specification are welcome and should
be directed to the technical proponent of the specification. A listing of
technical
proponents, including their organization designation and telephone number, is
on the Internet.
Recommended changes to a UFGS should be submitted as a
Criteria Change Request
(CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer choices or locations where
text must be supplied by the designer.
PART 1 GENERAL
1.1 REFERENCES
NOTE: This paragraph is used to list the publications cited in the text of
the guide specification. The publications are referred to in the text by basic
designation only and listed in this paragraph by organization, designation,
date, and title.
Use the Reference Wizard's Check Reference feature when you add a RID outside
of the Section's Reference Article to automatically place the reference in the
Reference Article. Also use the Reference Wizard's Check Reference feature
to update the issue dates.
References not used in the text will automatically be deleted from this section
of the project specification when you choose to reconcile references in the
publish print process.
The publications listed below form a part of this specification to the extent referenced. The publications are
referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA) |
|
AA DAF-45 | | (2003) Designation System for Aluminum Finishes |
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) |
|
AAMA 101 | | (2002) Voluntary Specifications for Aluminum,
Vinyl (PVC) and Wood Windows and Glass Doors |
|
AAMA 2603 | | (2002) Voluntary Specification, Performance
Requirements and Test Procedures for Pigmented
Organic Coatings on Aluminum Extrusions and
Panels |
|
AAMA 2604 | | (2002) Voluntary Specification, Performance
Requirements and Test Procedures for High Performance
Organic Coatings on Aluminum Extrusions and
Panels |
ASTM INTERNATIONAL (ASTM) |
|
ASTM D 1784 | | (2003) Rigid Poly(Vinyl Chloride) (PVC) Compounds
and Chlorinated Poly(Vinyl Chloride) (CPVC)
Compounds |
|
ASTM D 3656 | | (2004) Insect Screening and Louver Cloth Woven
from Vinyl-Coated Glass Yarns |
SCREEN MANUFACTURERS ASSOCIATION (SMA) |
|
SMA 1004 | | (1987; R 1998) Aluminum Tubular Frame Screens
for Windows |
WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA) |
|
WDMA I.S. 4 | | (2000) Water-Repellent Preservative Non-Pressure
Treatment for Millwork |
1.2 SUBMITTALS
NOTE: Review submittal description (SD) definitions in Section 01330 SUBMITTAL
PROCEDURES and edit the following list to reflect only the submittals required
for the project. Submittals should be kept to the minimum required for adequate
quality control.
A “G” following a submittal item indicates that the submittal requires Government
approval. Some submittals are already marked with a “G”. Only delete an existing
“G” if the submittal item is not complex and can be reviewed through the Contractor’s
Quality Control system. Only add a “G” if the submittal is sufficiently important
or complex in context of the project.
For submittals requiring Government approval on Army projects, a code of up
to three characters within the submittal tags may be used following the "G"
designation to indicate the approving authority. Codes for Army projects using
the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO"
for District Office (Engineering Division or other organization in the District
Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project
Office. Codes following the "G" typically are not used for Navy, Air Force,
and NASA projects.
Choose the first bracketed item for Navy, Air Force and NASA projects, or choose
the second bracketed item for Army projects.
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation
are [for Contractor Quality Control approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for the Government.] The following shall
be submitted in accordance with Section
01330
01330
01330 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Wood windows[; G][; G, [_____]]
Indicate elevations of units, full-size sections, fastenings, methods of installation and
anchorage, method of glazing, locations of operating hardware, mullion details, method and material
for weatherstripping, [bar and muntin layouts,] method of attaching [insect screens] [storm
windows], details of installation, and connections with other work.
SD-03 Product Data
Wood windows[; G][; G, [_____]]
SD-08 Manufacturer's Instructions
Wood windows
Submit manufacturer's written instructions for installation.
SD-10 Operation and Maintenance Data
Wood windows, Data Package 1; [; G][; G, [_____]]
Submit data package in accordance with Section
01781
01781
01781 OPERATION AND MAINTENCNE DATA.
1.3 DELIVERY AND STORAGE
Deliver windows to site in sealed undamaged cartons or in palletized multiple units. Protect from damage, dampness
and extreme temperature or humidity changes. Store under cover in well-ventilated enclosed space. Do not store
in a building under construction until concrete, masonry, and plaster are dry. Replace defective or damaged
windows.
PART 2 PRODUCTS
2.1 WOOD WINDOWS
NOTE: If window cleaning anchors are required, add:
"Window cleaning anchors to be stainless-steel, conforming to ASME A39.1. Reinforce
windows and frames for reception of anchors, and securely anchor window frames
to wall construction for window cleaning anchors."
NOTE: Where operating hardware is located 1980 mm 6 feet 6 inches or more above
floor, specify poles and pole-operated handles to operate windows.
NOTE: Show locations where storm units are to be installed. Windows for equipment
rooms, laundry rooms, and similar spaces should not be provided with storm units.
Storm windows are not required over double-glazed insulating type windows.
Specify window screens in medical facilities, food preparation areas, dining
areas, sleeping areas, and similar locations. Locations should be shown.
Wood windows shall consist of complete units including sash, glass, frame, weatherstripping, [insect screen,]
and hardware. Window units shall meet the Grade 40 requirements of
AAMA 101, except maximum air infiltration
shall not exceed
0.00016 cu m per second 0.34 CFM per linear foot of sash crack when tested under uniform static
air pressure difference of
75 pascals 1.57 psf. In addition to general hardware requirements of
AAMA 101, provide
hardware for various window types as indicated below. Glass and glazing materials shall conform to Section
08800
08800
08800 GLAZING. [Storm windows shall conform to Section
08582
08582
08582 ALUMINUM STORM WINDOWS]. [Wood members which will
receive transparent finish shall be in one piece, not finger-jointed.]
2.1.1 Single-Hung and Double-Hung Windows
NOTE: Double-hung or single-hung windows should be used for living quarters,
where storm sash are to be provided or window air-conditioners used. Single-hung
have less air leakage and should be considered over double-hung where feasible.
Provide with one sash fastener and two sash lifts, except provide one sash lift when window is fitted with a
balance that counterbalances weight of sash.
2.1.2 Awning Windows (Top Hinged)
Awning window ventilators in same bay shall operate [separately] [in unison]. Provide two or more hinges, pivots,
or sash-supporting arms for each operative sash to allow easy operation, substantial support and cleaning of
both sides of sash from inside. Provide latches for securing each sash if operating devices do not include locking
features. Provide operating devices for controlling position of sash, including full open, tight close, and intermediate
firm hold. Operating devices shall include rotary operators of worm-gear type with wear-resistant and impact-resistant
gears or lever operators of lever handle, off-set arm type. Venting sash shall have corrosion resistant steel
hinges connected to top and bottom rails of sash. When lever operators are used, operating arms shall be adjustable
so that even sash edge contact can be maintained.
2.1.3 Casement Windows
Provide two or more hinges, pivots, or sash-supporting arms for each operative sash to allow easy operation,
substantial support and cleaning of both sides of sash from inside. Provide latches for securing each sash if
operating devices do not include locking features. Provide operating devices for controlling the position of
the operative sash, including full open, tight close, and intermediate firm hold. Operating devices shall include
rotary gears and adjustable operating arms so that even sash contact can be maintained.
2.1.4 Horizontal-Sliding Windows
Provide latches, pulls, and corrosion resistant steel slides necessary to control and secure window. Provide
for cleaning of both sides of sash from inside.
2.1.5 Stationary Windows
Provide fixed sash and basic frame in accordance with AAMA 101.
2.2 FINISHES
[2.2.1 Paint
Furnish windows with factory-primed surfaces which will be exempt from first paint coat application required
in Section
09900
09900
09900 PAINTS AND COATINGS.
][2.2.2 Vinyl (PVC) Cladding
NOTE: Select the applicable paragraphs(s) from the following:
Preservative treat all basic wood frame and sash members in accordance with WDMA I.S. 4, except do not use pentachlorophenol.
Clad all exterior surfaces with rigid polyvinyl sheathing, complying with ASTM D 1784, class 14344-C, not less
that 0.9 mm35 mil average thickness.
][2.2.3 Aluminum Cladding
Preservative treat all basic wood frame and sash members in accordance with WDMA I.S. 4, except do not use pentachlorophenol.
Clad all exterior surfaces with roll formed aluminum with joints sealed during assembly. Aluminum clad frames
and sash shall meet performance requirements of AAMA 101.
2.2.3.1 Aluminum Finish
Factory finish with [anodic coating] [or] [organic coating].
2.2.3.2 Anodic Coating
NOTE: Select the applicable paragraphs(s) from the following:
Conform to AA DAF-45. Finish shall be [clear (natural), designation AA-M10-C22-A31, Architectural Class II 0.010
to 0.0175 mm 0.4 mil to 0.7 mil] [clear (natural), designation AA-M10-C22-A41, Architectural Class I 0.0175 mm
0.7 mil or thicker] [integral color-anodized, designation AA-M10-C22-A32, Architectural Class II 0.010 to 0.0175
mm 0.4 mil to 0.7 mil] [integral color-anodized, designation AA-M10-C22-A42, Architectural Class I 0.0175 mm
0.7 mil or thicker] [electrolytically deposited color-anodized designation AA-M10-C22-A34, Architectural Class
II 0.010 to 0.0175 mm 0.4 mil to 0.7 mil] [electrolytically deposited color-anodized, designation AA-M10-C22-A44,
Architectural Class I 0.0175 mm 0.7 mil or thicker]. [Color shall be [_____] [as indicated].]
2.2.3.3 Organic Coating
Clean and prime exposed aluminum surfaces. Provide [baked enamel finish in accordance with AAMA 2603 with total
dry film thickness not less than 0.020 mm0.8 mil] [high performance finish in accordance with AAMA 2604 with
total dry film thickness of not less than 0.030 mm 1.2 mils]. Finish color [_____] [as indicated].
][2.3 INSECT SCREENS
ASTM D 3656, Class 2, 18 by 14 mesh, color [charcoal] [grey] [_____]. Aluminum frames to meet SMA 1004.
][2.4 STORM SASH
][2.4.1 Finishes
Factory finish exposed aluminum surfaces with anodic coating or organic coating.
]PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Wood and Wood Clad Windows
Install in accordance with the approved installation instructions. Securely anchor windows in place.
[3.1.2 Insect Screen
Install screen panels in accord with manufacturer's instructions. Install aluminum framed screens in accord
with SMA 1004.
][3.1.3 Storm Windows
Install storm windows in accordance with manufacturer's standards and instructions.
]3.2 ADJUSTMENTS
Make final adjustment for proper operation of ventilating unit after glazing. Make adjustments to operating
sash or ventilators to assure smooth operation. Units shall be weathertight when locked closed.
3.3 CLEANING
Clean windows on both exterior and interior in accordance with manufacturer's recommendations.
-- End of Section --