Conveyor Belt Ventilation

Conveyor Belt Ventilation
Text Version

Conveyor Belt Ventilation

Conveyor Types:

  1. Conveyor transfer less than 3' fall. For greater fall, provide additional exhaust at lower belt (see #3).
    he = 0.25 VPd
  2. Conveyor to elevator with magnetic separator.
    he = 0.25 VPd
  3. Chute to belt transfer and conveyor transfer, greater than 3' fall. Use additional exhaust for dusty material as follows:
    Belt width 12"-36", Q = 700 cfm
    Belt width above 36", Q = 1,000 cfm
    he = 0.25 VPd
    Note: Dry, very dusty materials may require exhaust flowrates 1.5 to 2.0 times stated values.
Design Data From American Conference of Governmental Industrial Hygienists (ACGIH®), Figure VS-50-20, Industrial Ventilation : A Manual of Recommended Practice, 23rd Edition. Copyright 1998. Reprinted with permission.