Recommended Residential Construction for the Gulf Coast Building on Strong and Safe Foundations FEMA 550 / July 2006 Appendix C. Assumptions Used in Design Gulf Coast Foundation Designs The foundation designs proposed in Appendix A are based on the following standards and codes: ASCE 7-02 Minimum Design Loads for Buildings and Other Structures American Society of Civil Engineers (ASCE) ACI 530-02/ASCE 5-02/TMS 402-02 Building Code Requirements for Masonry Structures American Society of Civil Engineers (ASCE) American Concrete Institute (ACI) The Masonry Society (TMS) ACI 318-02 Building Code Requirements for Structural Concrete American Concrete Institute ANSI/AFPA NDS-2001 National Design Specifications for Wood Construction American Forest & Paper Association (AF&PA) American Wood Council IRC-2003 2003 International Residential Code for One- and Two-Family Dwellings International Code Council (ICC) To provide flexibility for the builder, a range of dead loads and building dimensions was used for calculating reactions on the foundation elements. For uplift and overturning analyses, the structure was assumed to be relatively light and narrow, and constructed with a relatively low-sloped roof. For sliding analyses, the home was considered relatively deep and constructed with a steeper roof slope. For the gravity loading analysis, a heavier structure was assumed. Dead Loads For Use in ASCE 7-02 ASD Uplift/Overturning Load Combination #7 (0.6D + W +H) First Floor - 8 psf - Vinyl flooring, 5/8-inch plywood sub-floor and 2 by 8 joists 16 inches on centers Second Floor - 10 psf - First floor components plus 1 layer of ½-inch gypsum drywall Wall - 9 psf - Wood siding, 2 by 4 studs 16 inch on centers, ½-inch plywood wall sheathing, and one layer of ½-inch gypsum drywall Roof - 12 psf - 200 lb/sq asphalt roofing, 15 lb/sq felt, ½-inch plywood decking, 2 by 4 top and bottom truss chords 24 inches on centers, ½-inch gypsum drywall ceiling finish Dead Loads For Use in ASCE 7-05 ASD Gravity Load Combination #2 (D + H + F + L + T) First Floor - 16 psf - Dead loads increased 8 lb/sf to account for additional finishes like hardwood flooring (4 lb/sf), ½-inch slate (7 lb/sf), or thin set tile (5 lb/sf) Second Floor - 18 psf Wall - 10 psf - Wall weight increased to account for cement composite siding Roof - 12 psf Concrete - 150 psf - Normal weight concrete. Footings for continuous perimeter walls were also sized to support full height brick veneer at 40 psf. Masonry - 115 psf - Medium weight block Grout - 105 psf Brick Veneer - 40 psf Wind Loads Designs provided for 120 mph, 130 mph, 140 mph, and 150 mph zones (3-second gust wind speeds per ASCE 7-02). Wind analysis used Method 2 for buildings of all heights. Exposure Category C - Open terrain with scattered obstructions generally less than 30 feet in height; shorelines in hurricane-prone areas K subscript zt - 1 - No topographic effects (i.e., no wind speedup effects from hills, ridges, or escarpments) K subscript d - 0.85 - Wind directionality factor (for use with ASCE 7-02 load combinations) K subscript z, K subscript h - Velocity pressure coefficients for Exposure Category C Flood Loads V Zone - Breaking wave load from a wave with height 78 percent of stillwater depth (d subscript s) Flood velocity (fps) equal to (gd subscript s) superscript 1/2 up to a maximum of 10 fps (FEMA 55 Upper Bound) Coastal A Zone - Breaking wave load from 1½ foot up to a 3 foot high wave Flood velocity (fps) equal to (gd subscript s) superscript 1/2 up to a maximum of 5 fps (FEMA 55 Upper Bound) Non-Coastal A Zone - Breaking wave load up to a 1½ foot high wave Flood velocity (fps) equal to stillwater flood depth (d subscript s) (in feet) (FEMA 55 lower bound) Lateral Loads (on stem walls) Lateral earth pressures from saturated soils - 100 pounds per cubic foot (pcf) Surcharge for slab weight and first floor live load - 65 pounds per square foot (psf) Live Loads First Floor - 40 psf Second Floor -30 psf Roof - 20 psf Soil Bearing Capacity 1,500 psf Presumptive value for clay, sandy clay, silty clay, clayey silt, silt, and sandy silt (CI, ML, MH and CH) (2003 IRC) Building Dimensions Building Width - 14 ft (per module) Building Depth - max 42 ft - min 24 ft Shear Wall Spacing - max 42 ft Floor Height - 10 ft (floor to floor dimension) Roof Pitch Ratio - min 3:12, Uplift and overturning calculation - max 12:12, Sliding calculation Roof Overhang - 2 ft