Fire Extinguishers in Underground Coal Mines   [12/20/2007]
[PDF]
FR Doc E7-24747

[Federal Register: December 20, 2007 (Volume 72, Number 244)]
[Proposed Rules]               
[Page 72301-72307]
From the Federal Register Online via GPO Access [wais.access.gpo.gov]
[DOCID:fr20de07-20]                         

=======================================================================
-----------------------------------------------------------------------

DEPARTMENT OF LABOR

Mine Safety and Health Administration

30 CFR Part 75

RIN 1219-AB40

 
Fire Extinguishers in Underground Coal Mines

AGENCY: Mine Safety and Health Administration, Labor.

ACTION: Proposed rule; close of comment period.

-----------------------------------------------------------------------

SUMMARY: The Mine Safety and Health Administration (MSHA), is proposing 
to amend the current standard for the quantity and location of 
firefighting equipment and materials underground to ensure that they 
are readily available to quickly extinguish a fire. In lieu of the 
current requirements for rock dust and other firefighting materials, 
this proposed rule would allow the use of portable fire extinguishers 
in working sections of underground anthracite coal mines that have no 
electrical equipment at the face and produce less than 300 tons of coal 
per shift. The rule also would require an additional fire extinguisher 
in lieu of rock dust at temporary electrical installations in all 
underground coal mines.

DATES: All comments must be received at MSHA no later than midnight 
Eastern Standard Time on February 4, 2008.

ADDRESSES: (1) Identify all comments by ``RIN 1219-AB40'' and send them 
to MSHA as follows:
     Electronically through the Federal e-Rulemaking portal at 
http://www.regulations.gov or by e-mail to zzMSHA-comments@dol.gov.

     By facsimile to 202-693-9441.
     By mail or hand delivery to MSHA, Office of Standards, 
Regulations, and Variances, 1100 Wilson Boulevard, Room 2350, 
Arlington, Virginia 22209-3939. If comments are hand-delivered, please 
stop by the 21st floor first to check in with the receptionist.
    (2) MSHA will post all comments on the internet without change, 
including any personal information they may contain. Rulemaking 
comments can be accessed via the internet at http://www.msha.gov/regsinfo.htm
 or in person at MSHA's public reading room


[[Page 72302]]

at 1100 Wilson Boulevard, Room 2349, Arlington, Virginia.
    (3) Subscribe to MSHA's list serve at http://www.msha.gov/subscriptions/subscribe.aspx
 to receive an e-mail notification when 

MSHA publishes rulemaking documents in the Federal Register.
    Hearings: Public hearings will be scheduled if requested.
    Information Collection Requirements. Comments concerning the 
information collection requirements must be clearly identified as such 
and sent to both the Office of Management and Budget (OMB) and MSHA as 
follows:
    (1) To OMB: All comments may be sent by mail to the Office of 
Information and Regulatory Affairs, Office of Management and Budget, 
New Executive Office Building, 725 17th Street, NW., Washington, DC 
20503, Attn: Desk Officer for MSHA; and
    (2) To MSHA: Comments must be clearly identified by RIN: 1219-AB40 
as comments on the information collection requirements and transmitted 
to MSHA as indicated above under ADDRESSES.

FOR FURTHER INFORMATION CONTACT: Patricia W. Silvey at 202-693-9440 
(Voice), 202-693-9441 (Fax), or Silvey.Patricia@dol.gov (E-mail).

SUPPLEMENTARY INFORMATION: 

I. Introduction

    The existing safety standards under 30 CFR part 75, subpart L--Fire 
Protection, are designed to ensure that firefighting equipment and 
materials are readily available to quickly extinguish a fire and 
prevent its spread. Because of the explosive nature of coal dust and 
the possible presence of methane gas, there is great potential for a 
fire to spread to other areas of the underground coal mine. Historical 
records demonstrate that the consequences of a fire in an underground 
coal mine can be disastrous.

II. Background

    The Bureau of Mines in the U.S. Department of the Interior (Bureau) 
promulgated and enforced fire protection standards under the Federal 
Coal Mine Safety Act (30 U.S.C. 451-483). These standards continued in 
effect under the Federal Coal Mine Health and Safety Act of 1969 (Coal 
Act) through a transfer provision in the law. On November 20, 1970 (35 
FR 17890), the Bureau revised its standards addressing fire protection 
in underground coal mines. The revised standards continued in effect 
under the Federal Mine Safety and Health Act of 1977 (Mine Act) through 
a transfer provision in the law when the enforcement of mine safety and 
health standards was moved from the Department of the Interior to the 
Department of Labor. The standard addressed in this rule has not 
changed since that time.

A. Petition for Modification of a Mandatory Safety Standard

    Section 101(c) of the Mine Act allows a mine operator or the 
representative of miners to petition MSHA for a modification of an 
existing safety standard. After investigating each petition, MSHA may 
grant a modification from the application of a safety standard when 
MSHA determines that--
    (1) The alternative method for achieving the desired result will at 
all times guarantee no less than the same measure of protection as the 
existing standard, or
    (2) The application of the existing standard will result in a 
diminution of safety to miners at that mine.
    This proposed rule would eliminate the need for a mine operator to 
file a petition for modification of an existing standard in order to 
permit the use of portable fire extinguishers in lieu of rock dust and 
other firefighting materials in the working sections of underground 
anthracite coal mines that produce less than 300 tons of coal per shift 
and use no electrical equipment at the face.
    Also, many underground coal mine operators have filed petitions for 
modification to use portable fire extinguishers at temporary electrical 
installations. This proposed rule would eliminate the requirement for 
rock dust and instead would require portable fire extinguishers at 
underground temporary electrical installations. Adding this requirement 
would eliminate the need to petition for permission to use fire 
extinguishers at these locations.

B. Rock Dust for Fire Protection

    Rock dust is an inorganic, non-combustible dust, such as crushed 
limestone, that the mine operator spreads on coal surfaces to reduce 
the chance of stirring up an explosive suspension of coal dust. The 
rock dust also can work as a fire suppressant by smothering or 
quenching the flame. It is widely used in coal mining to reduce the 
likelihood of coal dust explosions or flame propagation. A single bag 
of rock dust weighs about 40 pounds when dry. In damp environments, a 
bag of rock dust will absorb water, rendering it unusable for fire 
prevention or suppression purposes. Damp rock dust becomes somewhat 
plastic in consistency and dries into a hard, brick-like mass. The 
presence of bags of rock dust can give a false sense of security for 
firefighting purposes because the rock dust can absorb water even 
through a sealed bag. The miner or mine operator can be unaware that 
the rock dust is useless as a fire suppressant until trying to use it. 
Bags of rock dust must be protected from moisture, checked frequently, 
and replaced if wet or hardened. This lifting and moving of heavy bags 
of rock dust increases the risk of personal injury for miners.

C. Requirements for Portable Fire Extinguishers

    Existing standard Sec.  75.1100-1 sets minimum requirements for the 
type and quality of firefighting equipment required in 30 CFR part 75, 
subpart L--Fire Protection. Paragraph (e) of Sec.  75.1100-1 describes 
the criteria for a portable fire extinguisher as follows:

(e) Portable fire extinguisher: A portable fire extinguisher shall 
be either (1) a multipurpose dry chemical type containing a nominal 
weight of 5 pounds of dry powder and enough expellant to apply the 
powder or (2) a foam-producing type containing at least 2\1/2\ 
gallons of foam-producing liquids and enough expellant to supply the 
foam. Only fire extinguishers approved by the Underwriters 
Laboratories, Inc., or Factory Mutual Research Corp., carrying 
appropriate labels as to type and purpose, shall be used. After 
March 30, 1971, all new portable fire extinguishers acquired for use 
in a coal mine shall have a 2A 10 BC or higher rating.

III. Section-by-Section Discussion

    Existing standard Sec.  75.1100-2 sets requirements for the 
quantity and location of firefighting equipment and materials in 
underground coal mines. At working sections, paragraph (a) requires 240 
pounds of rock dust (about six bags), two portable fire extinguishers, 
and a ready supply of water or dry chemical. At permanent electrical 
installations, paragraph (e)(1) requires two portable fire 
extinguishers or one having twice the minimum capacity specified for a 
portable fire extinguisher in existing Sec.  75.1100-1(e). Rock dust is 
not required at permanent electrical installations. At temporary 
electrical installations, however, paragraph (e)(2) requires one 
portable fire extinguisher and 240 pounds of rock dust.

A. Section 75.1100-2(a): Working Sections

    Existing Sec.  75.1100-2(a) includes different requirements for 
readily available firefighting equipment and materials in working 
sections based on the mine's production. Because anthracite coal mines 
typically produce only 10 to 20 tons of coal per shift, they

[[Page 72303]]

are covered by existing Sec.  75.1100-2(a)(2), which requires--

    (2) Each working section of coal mines producing less than 300 
tons of coal per shift shall be provided with two portable fire 
extinguishers, 240 pounds of rock dust in bags or other suitable 
containers, and at least 500 gallons of water and at least 3 pails 
of 10 quart capacity. In lieu of the 500 gallon water supply a 
waterline with sufficient hose to reach the working places, a 
portable water car (500 gallons capacity) or a portable all-purpose 
dry powder chemical car of at least 125-pounds capacity may be 
provided.

    These options, however, do not address or accommodate the typical 
conditions in the working sections of underground anthracite coal 
mines. This proposed rule would add new paragraph Sec.  75.1100-2(a)(3) 
to provide an additional compliance option for underground anthracite 
coal mines and make nonsubstantive format changes to Sec.  75.1100-
2(a)(2).
1. Addition of Sec.  75.1100-2(a)(3) for Underground Anthracite Coal 
Mines
    New paragraph Sec.  75.1100-2 would apply only to underground 
anthracite coal mines. Almost all of these mines still use mining 
methods that were developed over 150 years ago to suit their unique 
geological characteristics. Anthracite coal is a hard coal found in 
undulating, steeply pitched veins, and mined with slow, non-mechanized 
mining methods. In contrast, bituminous coal is softer and generally 
found in horizontal veins. Bituminous coal production uses highly 
mechanized methods and depends on electricity for face equipment.
    Anthracite mining uses methods and systems that rely on manual 
labor with little or no mechanization. Electricity that can cause or 
contribute to a fire hazard is usually non-existent near the face. 
Typically, anthracite coal mines operate face equipment using air 
driven motors for coal drills, air driven fans to supplement face 
ventilation, and air driven saws and hoists for the cutting and 
placement of timber.
    Mining conditions in underground anthracite coal mines are 
generally wet and removal of water from the face areas is a major 
problem. The steep grade permits natural water drainage in open, on-
grade ditches from the face area to a slope sump where it is stored and 
eventually pumped to a suitable water treatment area. Waterlines are 
seldom installed to the face.
    Anthracite coal has a low volatile ratio and the dust does not 
propagate an explosion. Anthracite coal's ignition temperature is high 
(925 to 970 degrees Fahrenheit) compared to bituminous coal's ignition 
temperature (700 to 900 degrees Fahrenheit). Thus, anthracite coal dust 
is harder to ignite than bituminous coal dust and the risk of a fire is 
lower in anthracite coal mines than in bituminous coal mines. There has 
been only one reported fire underground in an anthracite coal mine 
since implementation of the Mine Act. This fire occurred at a mine that 
used electrical equipment at the face.
    In summary, almost all underground anthracite coal mines are 
steeply sloped with little space underground for storage of 
firefighting equipment or materials; they use hand-operated or 
mechanical equipment, rather than electrical equipment (a potential 
ignition source), underground at the face where coal is mined; and they 
are wet, causing rock dust to become hard and unusable for 
firefighting. In addition, anthracite coal mine dust has low 
volatility, is difficult to ignite, and does not propagate an 
explosion.
2. Discussion of Alternative for Underground Anthracite Coal Mines
    Because of the uniqueness of the mining methods and conditions in 
underground anthracite mines, anthracite mine operators have petitioned 
MSHA to allow the use of only portable fire extinguishers to replace 
existing requirements where rock dust, water cars, and other water 
storage are not practical. The mine operators assert that the 
alternative method will at all times guarantee no less than the same 
measure of protection as that afforded by the standard. From 1994 
through 2004, MSHA received over 60 petitions for modification of 
existing paragraph (a)(2) of Sec.  75.1100-2 and granted 54 for working 
sections at underground anthracite coal mines. The rest were dismissed 
for reasons unrelated to the merits of the proposed alternative method. 
For example, one petition was dismissed because the mine went out of 
business. None of the petitions were denied for safety reasons. MSHA 
granted the petitions for a modification with the following conditions.

    1. Fire extinguisher(s) having at least four times the minimum 
capacity specified for a portable fire extinguisher in 30 CFR 
75.1100-1(e) shall be located no greater than 500 feet from the 
working face.
    2. Fire extinguisher(s) having at least six times the minimum 
capacity specified for a portable fire extinguisher in 30 CFR 
75.1100-1(e) shall be located at the entrance to the gangway at the 
bottom of the slope.

    There were no significant adverse comments filed on these 
petitions. Based on MSHA's experience and investigation of these 
petitions for modification, MSHA concluded that the use of fire 
extinguishers in the situations addressed is a safe alternative to 
existing requirements. The granted alternative method provides for a 
quick response to any fire on the section and does not reduce 
protection for miners. In addition, because there are a variety of fire 
extinguishers currently available, MSHA anticipates no problems in 
obtaining fire extinguishers.
    This proposed rule would incorporate the language from these 
granted petitions for modification into new paragraph Sec.  75.1100-
2(a)(3). The Agency has made changes to the language from these 
petitions to clarify the mine operator's responsibility regarding the 
size of fire extinguishers required. Thus, this proposed rule would 
eliminate the need to file a petition for modification to use only 
portable fire extinguishers, in lieu of the firefighting equipment and 
materials required by existing paragraph (a)(2), for fighting fires at 
working sections of underground anthracite coal mines that have no 
electrical equipment at the working section. The proposed rule would 
not apply to the few underground anthracite coal mines that use 
electrical equipment at the working section.

B. Section 75.1100-2(e): Electrical Installations

    Existing Sec.  75.1100-2(e) causes unnecessary compliance 
difficulties for some mines with temporary electrical installations 
underground. Under the existing standard, permanent and temporary 
electrical installations have different requirements for firefighting 
equipment and materials. Existing Sec.  75.1100-2(e) requires that--

    (e) Electrical installations. (1) Two portable fire 
extinguishers or one extinguisher having at least twice the minimum 
capacity specified for a portable fire extinguisher in Sec.  
75.1100-1(e) shall be provided at each permanent electrical 
installation.
    (2) One portable fire extinguisher and 240 pounds of rock dust 
shall be provided at each temporary electrical installation.
1. Characteristics of Underground Electrical Installations
    The difference between permanent and temporary underground 
electrical installations can be negligible in regard to their potential 
fire hazard. For example, MSHA generally considers electrical 
installations located outby the working section to be permanent and 
those on the working section to be temporary. However, MSHA considers a 
battery charging station to be temporary because it moves, even though 
it is outby the working section. If the electrical installation is in a 
fireproof

[[Page 72304]]

enclosure, then MSHA considers it to be permanent. If not, MSHA 
considers it temporary. MSHA considers a power center supplying the 
belt line to be permanent, but one supplying a portable compressor to 
be temporary. Typically, temporary electrical installations are 
unattended pumping stations located in remote areas of the mine, 
battery charging stations, power installation transformers, and section 
power centers for operating electrical face equipment.
2. Elimination of Separate Requirements for Permanent and Temporary 
Electrical Installations
    From 1994 through 2004, MSHA received 34 petitions for modification 
of paragraph (e)(2) of Sec.  75.1100-2 and granted all of them. The 
petitioners asserted that it is difficult to comply with the current 
standard for temporary electrical installations in wet and damp 
environments, such as pumping stations, because the rock dust becomes 
unusable for firefighting purposes. The mine operator must check these 
locations frequently to assure that the rock dust is kept dry for use 
in the event of a fire. The petitioners assert that the exclusive use 
of portable fire extinguishers as an alternative means of extinguishing 
fires is at least as effective as the existing standard. They also have 
asserted that, in some cases, portable fire extinguishers may be a 
safer fire suppressant because lifting the heavy bags of rock dust 
increases the risk of personal injury.
    In granting these petitions, MSHA acknowledged the tendency of rock 
dust to harden over time and become brick-like when exposed to 
humidity, which greatly reduces the value of the rock dust as a 
firefighting tool. MSHA has no evidence of adverse outcomes associated 
with these granted petitions. Although MSHA did not receive any 
comments contesting the granted petitions, MSHA received a few comments 
on the petitions requesting that the Agency require a minimum of two 
fire extinguishers as the alternative method. Two fire extinguishers 
may be preferable in some situations to allow two miners to fight the 
fire simultaneously or to provide a backup should one of the portable 
fire extinguishers fail.
3. Impact of This Proposed Rule
    This proposed rule would modify existing Sec.  75.1100-2(e) to 
eliminate the separate requirements for permanent and temporary 
electrical installations. It would remove the requirement for rock dust 
at temporary underground electrical installations and require two 
portable fire extinguishers, or one having twice the minimum capacity, 
at all electrical installations. Essentially, the proposed rule would 
make the requirements for fire extinguishers at temporary electrical 
installations identical to the current requirements at permanent 
electrical installations. The Agency has made changes to the regulatory 
language to clarify the mine operator's responsibility regarding the 
size of fire extinguishers required. This revision would not reduce 
protection for miners.
    MSHA believes that all of the proposed revisions offer greater 
flexibility, provide no less protection to affected miners, and do not 
result in a diminution of safety to miners.

IV. Executive Order 12866

    Executive Order (E.O.) 12866 requires that regulatory agencies 
assess both the costs and benefits of significant regulatory action. 
Under the Executive Order, a ``significant regulatory action'' is one 
meeting any number of specified conditions, including the following: 
Having an annual effect on the economy of $100 million or more; 
creating a serious inconsistency or interfering with an action of 
another agency; materially altering the budgetary impact of 
entitlements or the rights of entitlement recipients; or raising novel 
legal or policy issues. MSHA has determined that this proposed rule 
would not have an annual effect of $100 million or more on the economy 
and that, therefore, it is not an economically ``significant regulatory 
action'' under section 3(f) of E.O. 12866. MSHA, however, has concluded 
that the proposed rule is otherwise significant under Executive Order 
12866 because it raises novel legal or policy issues.

A. Population-at-Risk

    As of 2006, this proposed rule would apply to 670 underground coal 
mine operators employing 42,667 miners (excluding office workers).

B. Costs

    This proposed rule potentially would affect all coal mines that 
have temporary electrical installations underground and about 20 active 
underground anthracite coal mines. As described below, MSHA estimates 
that the annual cost savings of this proposed rule would be $2,366.\1\
---------------------------------------------------------------------------

    \1\ $2,366 = $929 (savings to new anthracite coal mines) + 
$1,436 (savings to new temporary electrical installations).
---------------------------------------------------------------------------

1. Costs of Portable Fire Extinguishers and Rock Dust
    MSHA experience indicates that a 10-to 20-pound fire extinguisher 
is the industry standard. In addition, existing standards already 
require the mine operator to inspect and maintain the fire 
extinguishers periodically and replace them as necessary. The portable 
fire extinguishers have a shelf life of about 4 years. The cost to 
refill an emptied fire extinguisher is about 25 percent of its initial 
cost of about $25.00 for an industrial strength 2A:10B:C nominal 5-
pound fire extinguisher. MSHA does not require mine operators to report 
fires lasting less than 10 minutes from time of discovery and, 
therefore, has no estimate of the frequency with which a portable fire 
extinguisher is used and refilled. MSHA considers the maintenance of 
portable fire extinguishers to be an essential business practice for 
underground coal mines.
    The cost for 240 pounds of rock dust (six 40-pound bags) is about 
$6.00 ($1.00 per bag). Although rock dust usually does not require 
maintenance, it has to be replaced routinely in wet or damp 
environments, or otherwise protected to prevent it from becoming 
unusable. The shelf life of rock dust varies considerably in damp or 
wet environments. In addition to the labor cost for routine checking 
and replacing bags of rock dust, the cost associated with heavy, re-
sealable plastic bags or other methods of prolonging the shelf life of 
rock dust under these conditions is about $2 per bag.
2. Cost Savings for New Underground Anthracite Coal Mines
    MSHA estimates that this proposed rule would have no cost impact on 
the 20 active underground anthracite coal mines because, currently, 
they are operating under an alternative method that allows them to 
provide and rely solely on portable fire extinguishers for firefighting 
on the working section. This proposed rule, however, would benefit new 
underground anthracite coal mines by eliminating the need for the mine 
operator to file a petition for modification in order to provide and 
rely solely on portable fire extinguishers in lieu of the water and 
rock dust required by the existing standard.
    MSHA estimates that the average cost of filing a petition for 
modification is $465. MSHA estimates that it takes a mine supervisor, 
earning $57.82 per hour, 8 hours to prepare the petition for 
modification and that, on average, it takes a clerical worker, earning 
$20.96 per hour, 0.1 hours to copy and mail a petition.\2\ On average, 
two new underground anthracite coal mines open

[[Page 72305]]

each year.\3\ Therefore, the associated annual cost savings for new 
underground anthracite coal mines would be about $929.\4\
---------------------------------------------------------------------------

    \2\ $464.66 = (8 hours x $57.82) + (0.1 hour x $20.96).
    \3\ This is the average number of underground anthracite coal 
mines that opened in each year from 1999-2005.
    \4\ $929 = 2 petitions x $464.66 per petition.
---------------------------------------------------------------------------

3. Cost Savings for Temporary Electrical Installations at Underground 
Coal Mines
    Existing paragraph (e)(1) of Sec.  75.1100-2 requires two portable 
fire extinguishers, or one fire extinguisher having at least twice the 
minimum capacity specified in existing Sec.  75.1100-1(e), at each 
permanent underground electrical installation. Existing paragraph 
(e)(2) of Sec.  75.1100-2 requires one portable fire extinguisher and 
240 pounds of rock dust at each temporary underground electrical 
installation. This proposed rule would eliminate the distinction 
between permanent and temporary electrical installations. It would 
modify existing Sec.  75.1100-2(e) by removing the sub-paragraph 
designations (1) and (2) and applying the requirements for permanent 
electrical installations currently in paragraph (1) to all underground 
electrical installations. For the purpose of this analysis, MSHA 
estimates that most existing temporary electrical installations are 
already in compliance with this proposed rule because they contain two 
portable fire extinguishers or one having at least twice the minimum 
capacity.
    As previously noted, from 1994 through 2004, MSHA received and 
granted 34 petitions for modification of existing Sec.  75.1100-
2(e)(2). This averages to be about 3.1 petitions per year. Under the 
proposed rule, it would be unnecessary for a mine operator to file a 
petition for modification to obtain permission to rely exclusively on 
fire extinguishers for fighting fires at the mine's temporary 
electrical installations. Based on 3.1 petitions per year at an average 
cost of $465 for filing a petition for modification, MSHA estimates 
that the annual cost savings would be about $1,436 for underground coal 
mines.\5\
---------------------------------------------------------------------------

    \5\ $1,436 = 3.1 petitions x $464.66 per petition.
---------------------------------------------------------------------------

C. Benefits

    The proposed rule would allow the exclusive use of portable fire 
extinguishers in certain locations in the mine without the need for a 
mine operator to file a petition for modification and wait for MSHA 
approval.
    The most significant benefit is that rock dust, that can quickly be 
rendered ineffective by dampness, can be replaced immediately by a more 
effective and reliable fire suppressant, a portable fire extinguisher. 
An additional advantage of portable fire extinguishers is that they are 
easier to transport. A mine operator will usually be able to replace a 
damaged or spent fire extinguisher more quickly than 240 pounds of rock 
dust. MSHA also can reasonably anticipate a decreased risk of personal 
injury related to lifting and moving heavy bags of rock dust that have 
become hard and unusable.\6\
---------------------------------------------------------------------------

    \6\ MSHA injury data contain 332 injuries between 1999 and 
September 2005 where the phrase ``rock dust'' appears in the 
accident narrative. Of these 332 injuries, 120 ([ap]39%) involved 
lifting, carrying, or moving rock dust or bags of rock dust.
---------------------------------------------------------------------------

D. Feasibility

    MSHA has concluded that the requirements of the proposed rule would 
be both technologically and economically feasible. This proposed rule 
would be technologically feasible because it would not be technology-
forcing nor involve activities on the frontiers of scientific 
knowledge. This proposed rule would be economically feasible because it 
provides a cost saving to underground coal mines. Cost savings are 
based on new underground anthracite coal mine operators not having to 
file petitions for modification to use portable fire extinguishers in 
lieu of rock dust and other fire fighting materials at the working 
sections of underground anthracite coal mines that use no electrical 
equipment at the face and produce less than 300 tons of coal per shift. 
Likewise, there would be a cost savings for both existing and new 
underground coal mine operators not having to file petitions for 
modification to use portable fire extinguishers in lieu of rock dust at 
temporary underground electrical installations.

V. The Regulatory Flexibility Act (RFA) and the Small Business 
Regulatory Enforcement Fairness Act (SBREFA)

    Pursuant to the Regulatory Flexibility Act (RFA) of 1980 as amended 
by the Small Business Regulatory Enforcement Fairness Act (SBREFA), 
MSHA has analyzed the impact of the proposed rule on small businesses. 
Further, MSHA has made a determination with respect to whether or not 
MSHA can certify that the proposed rule would not have a significant 
economic impact on a substantial number of small entities that are 
covered by this rulemaking. Under the SBREFA amendments to the RFA, 
MSHA must include in the rule a factual basis for this certification. 
If a rule will have a significant economic impact on a substantial 
number of small entities, MSHA must develop a regulatory flexibility 
analysis.

A. Definition of a Small Mine

    Under the RFA, in analyzing the impact of a rule on small entities, 
MSHA must use the Small Business Administration (SBA) definition for a 
small entity or, after consultation with the SBA Office of Advocacy, 
establish an alternative definition for the mining industry by 
publishing that definition in the Federal Register for notice and 
comment. MSHA has not taken such an action and, consequently, must use 
the SBA definition. The SBA defines a small entity in the mining 
industry as an establishment with 500 or fewer miners.
    MSHA has also looked at the impacts of MSHA's rules on a different 
subset of mines that MSHA and the mining community have traditionally 
referred to as ``small mines,'' those having fewer than 20 miners. In 
general, these ``small mines'' differ from mines employing 20 or more 
miners not only in the number of miners, but also in economies of scale 
in material produced, in the type and amount of production equipment, 
and in supply inventory. Therefore, their costs of complying with 
MSHA's rules and the impact of the rules on them will also tend to be 
different. It is for this reason that ``small mines'' employing fewer 
than 20 miners are of special concern to us.
    This analysis complies with the legal requirements of the RFA for 
an analysis of the impacts on ``small entities'' while continuing 
MSHA's traditional definition of ``small mines.'' MSHA concludes that 
the Agency can certify that the proposed rule would not have a 
significant economic impact on a substantial number of small entities 
that are covered by this rulemaking. MSHA has determined that this is 
the case both for mines affected by this rulemaking with fewer than 20 
miners and for mines affected by this rulemaking with 500 or fewer 
miners.

B. Factual Basis for Certification

    This proposed rule would provide at least the same level of 
protection for miners as the current standard. It would result in a net 
cost savings and have no adverse economic impact on the underground 
coal mining industry.
    MSHA estimated that 2006 production for underground coal mines was 
7,817,859 tons for mines that had fewer than 20 miners and 277,634,777 
tons for mines that had 500 or fewer miners. Using the 2005 price of 
underground coal of $36.42 per ton, MSHA estimates the 2006 underground 
coal revenues to be about $285 million

[[Page 72306]]

for mines employing fewer than 20 miners and $10.1 billion for mines 
employing 500 or fewer miners. Using either MSHA's traditional 
definition of a small mine (those having fewer than 20 miners) or SBA's 
definition of a small mine (those having 500 or fewer miners), MSHA 
estimates that the proposed rule would result in a savings in the 
compliance cost for underground coal mines.

VI. Paperwork Reduction Act of 1995

    Due to this rulemaking, mine operators would no longer have to 
petition MSHA for a modification of existing paragraphs (a)(2) and 
(e)(2) of Sec.  75.1100-2 in order to rely exclusively on fire 
extinguishers for firefighting purposes. Existing Office of Management 
and Budget (OMB) paperwork package 1219-0065 includes the annual 
paperwork burden related to the preparation and filing of petitions 
with MSHA, including petitions for modification to use fire 
extinguishers. This proposed rule would reduce the paperwork burden in 
OMB paperwork package 1219-0065 by $2,366 and 41 hours annually.\7\
---------------------------------------------------------------------------

    \7\ $2,366 = $929 (savings for new anthracite coal mines) + 
$1,436 (savings for temporary electrical installations) and 41 hours 
= (8 + 0.1) hours per petition x (2 + 3) petitions.
---------------------------------------------------------------------------

    Existing OMB paperwork package 1219-0054 includes the annual 
paperwork burden related to examining fire extinguishers every 6 months 
and writing the date of the examination on a tag attached to the fire 
extinguisher. MSHA estimates that the paperwork burden for examining 
and tagging additional fire extinguishers at temporary electrical 
installations would be negligible because almost all temporary 
electrical installations are already in compliance.

VII. Other Regulatory Considerations

A. The Unfunded Mandates Reform Act of 1995 and Executive Order 12875: 
Enhancing the Intergovernmental Partnership (58 FR 58093)

    This proposed rule would not include any Federal mandate that may 
result in increased expenditures by State, local, or tribal 
governments; nor would it increase private sector expenditures by more 
than $100 million annually; nor would it significantly or uniquely 
affect small governments. Accordingly, the Unfunded Mandates Reform Act 
(2 U.S.C. 1501 et seq.) requires no further agency action or analysis.

B. The Treasury and General Government Appropriations Act of 1999: 
Assessment of Federal Regulations and Policies on Families

    This proposed rule would have no affect on family well-being or 
stability, marital commitment, parental rights or authority, or income 
or poverty of families and children. Accordingly, section 654 of the 
Treasury and General Government Appropriations Act of 1999 (5 U.S.C. 
601 note) requires no further agency action, analysis, or assessment.

C. Executive Order 12630: Government Actions and Interference With 
Constitutionally Protected Property Rights (53 FR 8859)

    This proposed rule would not implement a policy with ``takings'' 
implications. Accordingly, Executive Order 12630 requires no further 
agency action or analysis.

D. Executive Order 12988: Civil Justice Reform (61 FR 4729)

    This proposed rule was written to provide a clear legal standard 
for affected conduct and was carefully reviewed to eliminate drafting 
errors and ambiguities, so as to minimize litigation and undue burden 
on the federal court system. Accordingly, this proposed rule meets the 
applicable standards provided in section 3 of Executive Order 12988.

E. Executive Order 13045: Protection of Children From Environmental 
Health Risks and Safety Risks (62 FR 19885)

    This proposed rule would have no adverse impact on children. 
Accordingly, Executive Order 13045, as amended by Executive Orders 
13229 and 13296, requires no further agency action or analysis.

F. Executive Order 13132: Federalism (64 FR 43255)

    This proposed rule would not have ``federalism implications'' 
because it would not ``have substantial direct effects on the states, 
on the relationship between the national government and the states, or 
on the distribution of power and responsibilities among the various 
levels of government.'' Accordingly, Executive Order 13132 requires no 
further agency action or analysis.

G. Executive Order 13175: Consultation and Coordination With Indian 
Tribal Governments (63 FR 27655)

    This proposed rule would not have ``tribal implications'' because 
it would not ``have substantial direct effects on one or more Indian 
tribes, on the relationship between the federal government and Indian 
tribes, or on the distribution of power and responsibilities between 
the federal government and Indian tribes.'' Accordingly, Executive 
Order 13175 requires no further agency action or analysis.

H. Executive Order 13211: Actions Concerning Regulations That 
Significantly Affect Energy Supply, Distribution, or Use (66 FR 28355)

    This proposed rule would not be a ``significant energy action'' 
because it would not be ``likely to have a significant adverse effect 
on the supply, distribution, or use of energy (including a shortfall in 
supply, price increases, and increased use of foreign supplies).'' 
Accordingly, Executive Order 13211 requires no further agency action or 
analysis.

I. Executive Order 13272: Proper Consideration of Small Entities in 
Agency Rulemaking (67 FR 53461)

    MSHA has thoroughly reviewed this proposed rule to assess and take 
appropriate account of its potential impact on small businesses, small 
governmental jurisdictions, and small organizations. As discussed in 
section V of this preamble, MSHA has determined and certified that this 
proposed rule would not have a significant economic impact on a 
substantial number of small entities. Accordingly, Executive Order 
13272 requires no further agency action or analysis.

VIII. Petitions for Modification

    On the effective date of a final rule, all existing granted 
petitions for modification for the use of fire extinguishers in lieu of 
rock dust and other firefighting materials on working sections in 
underground anthracite coal mines and at temporary electrical 
installations in underground coal mines under Sec.  75.1100-2 
paragraphs (a)(2) and (e)(2), respectively, would be revoked. 
Thereafter, mine operators would be required to comply with the 
provisions of the final rule.

List of Subjects in 30 CFR Part 75

    Coal mines, Fire prevention, Mine safety and health, Safety, 
Underground mining.

     Dated: December 12, 2007.
Richard E. Stickler,
Assistant Secretary for Mine Safety and Health.
    For the reasons discussed in the preamble, the Mine Safety and 
Health Administration is proposing to amend 30 CFR part 75 as follows:

[[Page 72307]]

PART 75--MANDATORY SAFETY STANDARDS--UNDERGROUND COAL MINES

    1. The authority citation for part 75 continues to read as follows:

    Authority: 30 U.S.C. 811.

    2. Amend Sec.  75.1100-2 by revising paragraph (a)(2), adding 
paragraph (a)(3), and revising paragraph (e) to read as follows:


Sec.  75.1100-2  Quantity and location of firefighting equipment.

    (a) * * *
* * * * *
    (2) Each working section of coal mines producing less than 300 tons 
of coal per shift shall be provided with the following:
    (i) Two portable fire extinguishers; and
    (ii) 240 pounds of rock dust in bags or other suitable containers; 
and
    (iii) At least 500 gallons of water and at least three pails of 10-
quart capacity; OR a waterline with sufficient hose to reach the 
working places; OR a portable water car of at least 500-gallon 
capacity; OR a portable, all-purpose, dry-powder chemical car of at 
least 125-pound capacity.
    (3) As an alternative to paragraph (a)(2) of this section, each 
working section with no electrical equipment at the face of an 
anthracite coal mine producing less than 300 tons of coal per shift 
shall be provided with the following:
    (i) Portable fire extinguishers containing a total capacity of at 
least 30 pounds of dry chemical or 15 gallons of foam and located at 
the entrance to the gangway at the bottom of the slope; and
    (ii) Portable fire extinguishers containing a total capacity of at 
least 20 pounds of dry chemical or 10 gallons of foam and located 
within 500 feet from the working face.
* * * * *
    (e) Electrical installations. At each electrical installation, the 
operator shall provide two portable fire extinguishers or one having at 
least 10 pounds of dry chemical or 5 gallons of foam.
* * * * *
[FR Doc. E7-24747 Filed 12-19-07; 8:45 am]