STEADY STATE THERMAL PERFORMANCE OF CONCRETE MASONRY WALLS
Clear wall thermal analysis
Mortar effect
Grout effect
Overall wall thermal analysis
RESULTS OF THE STEADY STATE THERMAL MODELING
For clear wall thermal
analysis, six types of masonry wall units were considered during computer
modeling. For each shape of CMU thermal efficiency of insulation (TE) and clear
wall R-value were computed as a function of thermal resistivity of concrete
used in block production. A reduction of wall R-value caused by using mortar
was discussed as a function of thermal resistivity of block concrete for
uninsulated and insulated 2-core units. For uninsulated 2-core units, insulated
2-core units, cut-web units, uninsulated multicore units, and insulated
multicore units, a reduction of the wall R-value caused by grout was computed
as a function of thermal resistivity of block concrete. Overall wall thermal
analysis was performed for uninsulated 2-core units, insulated 2-core units,
cut-web units, uninsulated multicore units, and insulated multicore units.
Structural drawings of the wall details for solid CMU and for solid CMUs with
the serpentine and interlocking insulation inserts were not available for the
author, so they were not included in the overall wall analysis.
As shown in Figure 3, the thermal efficiency (TE) of the insulation
material in two-core, cut-web, and multicore units made of normal
density concrete varies from 20-40%. For solid units with interlocking
insulation inserts - shape B, TE varies from 30%-80%, and for shape A
units - 70%-90%. It can be observed that if CMUs are made of
lightweight concrete, the thermal efficiency of the insulation is higher. For
most of the insulated blocks made of lightweight concrete (except insulated
multicore CMUs), TE can reach 60%-90%. Insulation in multicore units is very
ineffective. For normal density
concrete, it is below 20%. The maximum
TE value for these multicore units made of very lightweight concrete will not
likely exceed 65%.
Thermal resistances of six
considered shapes of CMUs are depicted in Figure 4 as a function of thermal resistivity of block
concrete.
Solid CMUs are
normally produced of the lightweight concretes. For 12-in. thick units R-value
varies from about 5 to 10 hft2F/Btu
(0.8 - 1.7 m2 K/W).
As shown in Figure 4, the thermal performance of two-core
units made of normal-density concrete is very low; for an uninsulated
12-in. (30-cm) thick unit, the R-value is below 2 h•ft2F/Btu (0.35 m2K/W). Because of this, several companies offer many types of insulation
inserts that are supposed to improve the block’s thermal performance. Unfortunately, because the inserts are
located only in air cavities portioned with the concrete webs, they cannot
eliminate the thermal shorts through the transversal concrete webs. For
insulated units, the R-value remains below 3.5 h•ft2F/Btu (0.62 m2K/W). If two-core units are made of lightweight
concrete (not a common practice in the
U.S.), their R-values may be higher - about 4 h•ft2F/Btu (0.7 m2K/W) for uninsulated units, and
8 h•ft2F/Btu (1.4 m2K/W) for insulated units.
Cut-web CMUs were designed to reduce heat losses caused by
transversal concrete webs in two-core units. Many types of the insulation
inserts for the cut-web units are available in the U.S. market. Even if the concrete web height is radically
reduced (about 40% in simulated cut-web units), heat losses still occur through
the transversal concrete webs. It can
be observed in Figure 4 that the increase of the thermal resistance caused
by the reduction of concrete webs is minimal for units made of normal density
concretes (comparison of R-value between insulated two-core and cut-web units).
For the insulated 12-in. thick cut-web unit made of normal density
concrete, the R-value is below 5.4 h•ft2F/Btu (0.95 m2K/W).
R-values of the cut-web units made of lightweight concrete could
exceed 11 h•ft2F/Btu (1.94 m2K/W).
As shown in Figure 4, for multicore units made of normal density
concretes, the R-value of an uninsulated 12-in. (30-cm) thick
unit is below 3.5 h•ft2F/Btu (0.62 m2K/W) and for an insulated unit it is about 6.8
h•ft2/Btu (1.2 m2K/W).
It is interesting that the R-value of an uninsulated multicore
unit is as high as the R-value of an insulated two-core unit. For insulated multicore units made of
lightweight concrete, the R-value could exceed 19 h•ft2F/Btu (3.35 m2K/W).
Solid blocks with interlocking insulation inserts are usually made of lightweight concretes. As shown in Figure 4, for solid units with integral insulation inserts
-shape A, the R-value can exceed 18 h•ft2F/Btu (3.17 m2K/W). For shape B unit, R-value
can reach 20 h•ft2F/Btu (3.52 m2K/W).
Note that all presented above R-values account only for
blocks themselves, they do not account
for mortar or grout.
The mortar joint area usually
covers 4%-10% of the total wall area.
Mortar may generate additional wall heat losses in masonry walls. Because of the complicated 3-dimmensional
character of the heat transfer in areas of mortar joints, the reduction of the
wall thermal resistance is seldom incorporated in the R-value
calculations. As shown in Figure 5, the R-value reduction can exceed 12% for two-core
units. The mortar effect increases when
the thermal resistivity of block concrete increases. A reduction of the influence of the heat losses through the
mortar on the wall R-value can be achieved by using less-conductive
mortars or decreasing the area of mortar joints. In many CMUs, side mortar is being replaced by the interlocking
means to connect adjacent units without the usage of mortar.
Construction of load-bearing
walls made of hollow-core blocks frequently requires installing
additional reinforcement and filling air cores with the grout. For all CMUs, grout effect decreases when
the concrete thermal resistivity increases.
For the grout of thermal resistivity 0.11 h•ft2F/BTU per in (0.77mK/W), the grout effect was depicted as
a function of the block concrete thermal resistivity. It can be observed in Figure 6, that cut-web units are less sensitive to the grout effect
(grout effect varies from 3%-7%).
For two-core units made of normal density concretes, reduction of
the R-value caused by the grout poured into the cores is about 10%. For two-core units made of lightweight
concrete, the grout effect is about 5%.
For uninsulated multicore CMUs, the grout effect remains in the 6%-12%
range. The R-value of insulated
multicore units is very sensitive to the local thermal bridges caused by cores
filled with grout. Reduction of the R-value
for these units may reach 30% for normal density concretes and 25% for
lightweight concretes.
Walls are not homogeneous
thermal barriers made from uniform components.
Wall details, such as corners or structural connections between wall and
ceiling, behave very differently from the clear wall. For example, in walls constructed of cut-web units, standard
two-core units have to be used for corners and wall openings [Insul Block
1992]. In all masonry systems, U-blocks are frequently used in bond beams and
cast in place lintels [Hoke 1988, Sparfil 1991]. Steel lintel angels are in
common use for window and door headers [Sparfil 1991]. Also, for most of
masonry wall systems, beams, girders and other concentrated loads shall bear on
the grouted blocks [Hoke 1988, NCMA 1975]. A concentration of highly conductive
materials (steel, concrete, grout) creates thermal shorts in locations of the
construction details in masonry walls. At present, the impact of the
construction details on the overall wall thermal performance is often
overlooked. This simplification can
lead to errors in predicting the energy efficiency of building envelopes.
Results of the whole wall
thermal analysis for uninsulated 2-core units, insulated 2-core units, cut-web
units, uninsulated multicore units, and insulated multicore units are
summarized in Figure 7. For all
listed above wall systems, two densities of concrete were considered during
modeling: for two-core and cut-web units: normal density concrete,
120 lb/ft3 (1,920 kg/m3) of thermal resistivity 0.19
h•ft2F/Btu per in. (1.32 mK/W), and for multicore
units: lightweight concrete, 40 lb/ft3
(640 kg/m3) of thermal resistivity 0.90 h•ft2F/Btu per in. (6.24 mK/W).
Geometries of wall details were
obtained from the following standard architectural drawings or system
manufacturers' design guides. Detailed description of wall details used for
computer modeling is presented in Tables 2, 3, and 4.
Wall detail | Description of wall detail | References |
clear wall | Thermal effect of mortar 0.2 h•ft2F/Btu per in. ( 1.4 mK/W) and grout 0.11 h•ft2F/Btu per in. ( 0.77 mK/W) installed with 16-in. ( 40-cm.)o.c., included. In case of insulated units: 1-7/8-in. ( 4.76-cm.) thick EPS inserts. | |
corner | standard 12-in. (30-cm.) corner units | NCMA 1975 p. 28. |
wall/ceiling | two courses of blocks with cores filled with grout, 4-in. ( 10-cm.) wood sill plate, 9-in. ( 22.5-cm.) joists, R-30 insulation. | Hoke 1988 p.189, |
wall/floor | two courses of units with cores filled with grout, 6-in. ( 15-cm.) joists, plus 8-in. (20-cm.) two-core block with cores filled with grout in case of uninsulated wall, or in case of insulated wall, 6-in. (15-cm.) solid block with 2-in. ( 5-cm.) thick EPS plate between block and joist. | NCMA 1975 p. 29 |
window, door header | 2 two-core 6-in. ( 15-cm.) units, plus 2 steel lintels 3-1/2x5x1/4-in. ( 8.9x12.5x.6-cm.) | Hoke 1988 p. 90 |
window, door side | standard two-core units | |
window sill | one row of two-core blocks with cores filled with grout |
Wall detail | Description of wall detail | References |
clear wall | Thermal effect of grout 0.11 h•ft2F/Btu per in. ( 0.77 mK/W) installed with 16-in. ( 40-cm.) o.c., included. Insulated units with 2-1/2-in. (6.4-cm.) thick EPS inserts | |
corner | standard 12-in. (30-cm.) two-core units with 2-1/2-in. ( 6.4-cm.) thick EPS inserts | Insul Block 1992 p. 4 |
wall/ceiling | One row of U-blocks with cores filled with grout, with 2-in. ( 5-cm.) thick EPS inserts, 4-in. ( 10-cm.) wood sill plate, 9-in. ( 22.5-cm.) joists, R-30 insulation | Hoke 1998 p. 189 |
wall/floor | One row of U-blocks with cores filled with grout, with 2-in. ( 5-cm.) thick EPS inserts, 6-in. ( 15-cm.) joists, 6-in. (15-cm.) solid block with 2-in.( 5-cm.) thick EPS plate between block and joist | NCMA 1975 p. 29 |
window, door header | 2 two-core 6-in. ( 15-cm.) units with 2-in. ( 5-cm.) thick EPS inserts, plus 2 steel lintels 3-1/2x5x1/4-in. ( 8.9x12.5x.6-cm.) | Hoke 1988 p. 390 |
window, door side | standard two-core units with 2-in. ( 5-cm.) thick EPS inserts | |
window sill | one row of two-core blocks with cores filled with grout |
Wall detail | Description of wall detail | References |
clear wall | 12-in. ( 30-cm.) multicore units with 3 rows of air cores. In case of insulated units all cores filled with EPS inserts. | |
corner | 12-in. (30-cm.) corner units with one row of air cores. | Sparfil 1991 p. 22 |
wall/ceiling | one course of multicore units with two rows of air cores filled with grout, 4-in. ( 10-cm.) wood sill plate, 9-in. ( 22.5-cm.) joists, R-30 insulation. | Sparfil 1991 p. 13 |
wall/floor | one course of multicore units with two rows of air cores filled with grout, 3/8-in. ( 1-cm.) concrete pillow, 6-in. ( 15-cm.) joists, plus 8-in. (20-cm.) multicore block with cores filled with EPS inserts. | Sparfil 1991 p. 14, Sparfil 1989 p. 11 |
window, door header | multicore units 12-in. ( 30-cm.) with center webs routed to fit steel lintels, 2 steel lintels 3-1/2x5x1/4-in. ( 8.9x12.5x.6-cm.). | Sparfil 1991 p. 12 |
window, door side | standard multicore units | |
window sill | standard multicore units |
For all considered wall
systems, except an uninsulated two-core unit wall, the R-values of
the wall details are 20%-50% lower than the R-value of the clear
wall. For the uninsulated two-core CMU system, the R-value of the clear
wall area is so low [1.56 h•ft2F/Btu (0.27 m2K/W)]
that the thermal performance of the wall details can actually increase the R-value
of the overall wall area. In the cut-web unit wall system, two-core
units are commonly used for the wall details.
For the cut-web unit wall, the R-value of the whole wall is about 12%
less than that of the clear wall. For
uninsulated multicore units, the clear wall R-value is almost equal to
the overall wall R-value. For
insulated multicore units, the whole wall R-value is 24% lower than the
clear wall R-value. It was
observed that for walls made of cut-web or insulated multicore units, R-values
of the three most significant wall details (corner, wall/ceiling, and
wall/floor details) are 25%-50% lower than the clear wall R-value. The wall/ceiling detail has the most
lowering impact on the overall wall R-value.
© 2001 Oak Ridge National Labs
Updated August 21, 2001 by Diane McKnight