Test 1 |
Tests performed Fall 2001 |
click
here for test specifics |
C-TEMP
weighted average of surface and joint TC's, climate side (°F)
|
28.4 |
M-TEMP
weighted average of surface and joint TC's, meter side (°F)
|
74.6 |
MA-AIR-T
average of 36 air TC's, meter side (°F)
|
79.7 |
M-BAF-T
average of 24 baffle TC's, meter side (°F)
|
78.2 |
C-AIR-T
average of 48 air TC's, climate side (°F)
|
26.1 |
MDIFFERC (°F)
Average temperature difference across metering box walls
|
-0.001 |
C-BAF-T
average of 36 baffle TC's, meter side (°F)
|
26.8 |
M-AIR-VC
air velocity, meter side (MPH)
|
0.52 |
C-AIR-VC
air velocity, climate side (MPH)
|
2.24 |
TMP-DC (Btu/Hr)
Total measured energy into metering box (Btu/hr)
|
416.5 |
∆T
temperature difference across sample wall
|
46.3 |
T(mean)
mean temperature across sample wall
|
51.5 |
Qmb
energy exchange through meter box walls (Btu/hr)
|
0.007 |
Mflank (Btu/Hr)
meter box flanking loss, determined by calibrations
|
4.834 |
Qwall
calculated energy flow through specimen wall (Qwall - Qsurr)
|
411.7 |
Face-To-Face Rwall
surface to surface R-value of wall (hr*ft2*°F/Btu)
|
7.2 |
Air-To-Air Ru wall
overall R-value of sample wall (air-to-air), Rms air + Rwall + Rcs air (hr*ft2*°F/Btu)
|
8.3 |
Rms air
meter side air film resistance (hr*ft2*°F/Btu)
|
0.744 |
Rcs air
climate side air film resistance (hr*ft2*°F/Btu)
|
0.325 |