[Code of Federal Regulations]
[Title 29, Volume 5]
[Revised as of January 1, 2007]
From the U.S. Government Printing Office via GPO Access
[CITE: 29CFR1910.304]

[Page 842-854]
 
                             TITLE 29--LABOR
 
CHAPTER XVII--OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT 
                                OF LABOR
 
PART 1910_OCCUPATIONAL SAFETY AND HEALTH STANDARDS--Table of Contents
 
                          Subpart S_Electrical
 
Sec.  1910.304  Wiring design and protection.

    (a) Use and identification of grounded and grounding conductors--(1) 
Identification of conductors. A conductor used as a grounded conductor 
shall be identifiable and distinguishable from all other conductors. A 
conductor used as an equipment grounding conductor shall be identifiable 
and distinguishable from all other conductors.
    (2) Polarity of connections. No grounded conductor may be attached 
to any terminal or lead so as to reverse designated polarity.
    (3) Use of grounding terminals and devices. A grounding terminal or 
grounding-type device on a receptacle, cord connector, or attachment 
plug may not be used for purposes other than grounding.
    (b) Branch circuits--(1) [Reserved]
    (2) Outlet devices. Outlet devices shall have an ampere rating not 
less than the load to be served.
    (c) Outside conductors, 600 volts, nominal, or less. Paragraphs 
(c)(1), (c)(2), (c)(3), and (c)(4) of this section apply to branch 
circuit, feeder, and service conductors rated 600 volts, nominal, or 
less and run outdoors as open conductors. Paragraph (c)(5) applies to 
lamps installed under such conductors.
    (1) Conductors on poles. Conductors supported on poles shall provide 
a horizontal climbing space not less than the following:
    (i) Power conductors below communication conductors--30 inches.
    (ii) Power conductors alone or above communication conductors: 300 
volts or less--24 inches; more than 300 volts--30 inches.
    (iii) Communication conductors below power conductors with power 
conductors 300 volts or less--24 inches; more than 300 volts--30 inches.
    (2) Clearance from ground. Open conductors shall conform to the 
following minimum clearances:
    (i) 10 feet--above finished grade, sidewalks, or from any platform 
or projection from which they might be reached.
    (ii) 12 feet--over areas subject to vehicular traffic other than 
truck traffic.
    (iii) 15 feet--over areas other than those specified in paragraph 
(c)(2)(iv) of this section that are subject to truck traffic.

[[Page 843]]

    (iv) 18 feet--over public streets, alleys, roads, and driveways.
    (3) Clearance from building openings. Conductors shall have a 
clearance of at least 3 feet from windows, doors, porches, fire escapes, 
or similar locations. Conductors run above the top level of a window are 
considered to be out of reach from that window and, therefore, do not 
have to be 3 feet away.
    (4) Clearance over roofs. Conductors shall have a clearance of not 
less than 8 feet from the highest point of roofs over which they pass, 
except that:
    (i) Where the voltage between conductors is 300 volts or less and 
the roof has a slope of not less than 4 inches in 12, the clearance from 
roofs shall be at least 3 feet, or
    (ii) Where the voltage between conductors is 300 volts or less and 
the conductors do not pass over more than 4 feet of the overhang portion 
of the roof and they are terminated at a through-the-roof raceway or 
approved support, the clearance from roofs shall be at least 18 inches.
    (5) Location of outdoor lamps. Lamps for outdoor lighting shall be 
located below all live conductors, transformers, or other electric 
equipment, unless such equipment is controlled by a disconnecting means 
that can be locked in the open position or unless adequate clearances or 
other safeguards are provided for relamping operations.
    (d) Services--(1) Disconnecting means--(i) General. Means shall be 
provided to disconnect all conductors in a building or other structure 
from the service-entrance conductors. The disconnecting means shall 
plainly indicate whether it is in the open or closed position and shall 
be installed at a readily accessible location nearest the point of 
entrance of the service-entrance conductors.
    (ii) Simultaneous opening of poles. Each service disconnecting means 
shall simultaneously disconnect all ungrounded conductors.
    (2) Services over 600 volts, nominal. The following additional 
requirements apply to services over 600 volts, nominal.
    (i) Guarding. Service-entrance conductors installed as open wires 
shall be guarded to make them accessible only to qualified persons.
    (ii) Warning signs. Signs warning of high voltage shall be posted 
where other than qualified employees might come in contact with live 
parts.
    (e) Overcurrent protection--(1) 600 volts, nominal, or less. The 
following requirements apply to overcurrent protection of circuits rated 
600 volts, nominal, or less.
    (i) Protection of conductors and equipment. Conductors and equipment 
shall be protected from overcurrent in accordance with their ability to 
safely conduct current.
    (ii) Grounded conductors. Except for motor running overload 
protection, overcurrent devices may not interrupt the continuity of the 
grounded conductor unless all conductors of the circuit are opened 
simultaneously.
    (iii) Disconnection of fuses and thermal cutouts. Except for service 
fuses, all cartridge fuses which are accessible to other than qualified 
persons and all fuses and thermal cutouts on circuits over 150 volts to 
ground shall be provided with disconnecting means. This disconnecting 
means shall be installed so that the fuse or thermal cutout can be 
disconnected from its supply without disrupting service to equipment and 
circuits unrelated to those protected by the overcurrent device.
    (iv) Location in or on premises. Overcurrent devices shall be 
readily accessible to each employee or authorized building management 
personnel. These overcurrent devices may not be located where they will 
be exposed to physical damage nor in the vicinity of easily ignitible 
material.
    (v) Arcing or suddenly moving parts. Fuses and circuit breakers 
shall be so located or shielded that employees will not be burned or 
otherwise injured by their operation.
    (vi) Circuit breakers. (A) Circuit breakers shall clearly indicate 
whether they are in the open (off) or closed (on) position.
    (B) Where circuit breaker handles on switchboards are operated 
vertically rather than horizontally or rotationally, the up position of 
the handle shall be the closed (on) position. (See Sec.  
1910.302(b)(3).)

[[Page 844]]

    (C) If used as switches in 120-volt, fluorescent lighting circuits, 
circuit breakers shall be approved for the purpose and marked ``SWD.'' 
(See Sec.  1910.302(b)(3).)
    (2) Over 600 volts, nominal. Feeders and branch circuits over 600 
volts, nominal, shall have short-circuit protection.
    (f) Grounding. Paragraphs (f)(1) through (f)(7) of this section 
contain grounding requirements for systems, circuits, and equipment.
    (1) Systems to be grounded. The following systems which supply 
premises wiring shall be grounded:
    (i) All 3-wire DC systems shall have their neutral conductor 
grounded.
    (ii) Two-wire DC systems operating at over 50 volts through 300 
volts between conductors shall be grounded unless:
    (A) They supply only industrial equipment in limited areas and are 
equipped with a ground detector; or
    (B) They are rectifier-derived from an AC system complying with 
paragraphs (f)(1)(iii), (f)(1)(iv), and (f)(1)(v) of this section; or
    (C) They are fire-protective signaling circuits having a maximum 
current of 0.030 amperes.
    (iii) AC circuits of less than 50 volts shall be grounded if they 
are installed as overhead conductors outside of buildings or if they are 
supplied by transformers and the transformer primary supply system is 
ungrounded or exceeds 150 volts to ground.
    (iv) AC systems of 50 volts to 1000 volts shall be grounded under 
any of the following conditions, unless exempted by paragraph (f)(1)(v) 
of this section:
    (A) If the system can be so grounded that the maximum voltage to 
ground on the ungrounded conductors does not exceed 150 volts;
    (B) If the system is nominally rated 480Y/277 volt, 3-phase, 4-wire 
in which the neutral is used as a circuit conductor;
    (C) If the system is nominally rated 240/120 volt, 3-phase, 4-wire 
in which the midpoint of one phase is used as a circuit conductor; or
    (D) If a service conductor is uninsulated.
    (v) AC systems of 50 volts to 1000 volts are not required to be 
grounded under any of the following conditions:
    (A) If the system is used exclusively to supply industrial electric 
furnaces for melting, refining, tempering, and the like.
    (B) If the system is separately derived and is used exclusively for 
rectifiers supplying only adjustable speed industrial drives.
    (C) If the system is separately derived and is supplied by a 
transformer that has a primary voltage rating less than 1000 volts, 
provided all of the following conditions are met:
    (1) The system is used exclusively for control circuits,
    (2) The conditions of maintenance and supervision assure that only 
qualified persons will service the installation,
    (3) Continuity of control power is required, and
    (4) Ground detectors are installed on the control system.
    (D) If the system is an isolated power system that supplies circuits 
in health care facilities.
    (2) Conductors to be grounded. For AC premises wiring systems the 
identified conductor shall be grounded.
    (3) Grounding connections. (i) For a grounded system, a grounding 
electrode conductor shall be used to connect both the equipment 
grounding conductor and the grounded circuit conductor to the grounding 
electrode. Both the equipment grounding conductor and the grounding 
electrode conductor shall be connected to the grounded circuit conductor 
on the supply side of the service disconnecting means, or on the supply 
side of the system disconnecting means or overcurrent devices if the 
system is separately derived.
    (ii) For an ungrounded service-supplied system, the equipment 
grounding conductor shall be connected to the grounding electrode 
conductor at the service equipment. For an ungrounded separately derived 
system, the equipment grounding conductor shall be connected to the 
grounding electrode conductor at, or ahead of, the system disconnecting 
means or overcurrent devices.

[[Page 845]]

    (iii) On extensions of existing branch circuits which do not have an 
equipment grounding conductor, grounding-type receptacles may be 
grounded to a grounded cold water pipe near the equipment.
    (4) Grounding path. The path to ground from circuits, equipment, and 
enclosures shall be permanent and continuous.
    (5) Supports, enclosures, and equipment to be grounded--(i) Supports 
and enclosures for conductors. Metal cable trays, metal raceways, and 
metal enclosures for conductors shall be grounded, except that:
    (A) Metal enclosures such as sleeves that are used to protect cable 
assemblies from physical damage need not be grounded; or
    (B) Metal enclosures for conductors added to existing installations 
of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable need 
not be grounded if all of the following conditions are met: (1) Runs are 
less than 25 feet; (2) enclosures are free from probable contact with 
ground, grounded metal, metal laths, or other conductive materials; and 
(3) enclosures are guarded against employee contact.
    (ii) Service equipment enclosures. Metal enclosures for service 
equipment shall be grounded.
    (iii) Frames of ranges and clothes dryers. Frames of electric 
ranges, wall-mounted ovens, counter-mounted cooking units, clothes 
dryers, and metal outlet or junction boxes which are part of the circuit 
for these appliances shall be grounded.
    (iv) Fixed equipment. Exposed non-current-carrying metal parts of 
fixed equipment which may become energized shall be grounded under any 
of the following conditions:
    (A) If within 8 feet vertically or 5 feet horizontally of ground or 
grounded metal objects and subject to employee contact.
    (B) If located in a wet or damp location and not isolated.
    (C) If in electrical contact with metal.
    (D) If in a hazardous (classified) location.
    (E) If supplied by a metal-clad, metal-sheathed, or grounded metal 
raceway wiring method.
    (F) If equipment operates with any terminal at over 150 volts to 
ground; however, the following need not be grounded:
    (1) Enclosures for switches or circuit breakers used for other than 
service equipment and accessible to qualified persons only;
    (2) Metal frames of electrically heated appliances which are 
permanently and effectively insulated from ground; and
    (3) The cases of distribution apparatus such as transformers and 
capacitors mounted on wooden poles at a height exceeding 8 feet above 
ground or grade level.
    (v) Equipment connected by cord and plug. Under any of the 
conditions described in paragraphs (f)(5)(v)(A) through (f)(5)(v)(C) of 
this section, exposed non-current-carrying metal parts of cord- and 
plug-connected equipment which may become energized shall be grounded.
    (A) If in hazardous (classified) locations (see Sec.  1910.307).
    (B) If operated at over 150 volts to ground, except for guarded 
motors and metal frames of electrically heated appliances if the 
appliance frames are permanently and effectively insulated from ground.
    (C) If the equipment is of the following types:
    (1) Refrigerators, freezers, and air conditioners;
    (2) Clothes-washing, clothes-drying and dishwashing machines, sump 
pumps, and electrical aquarium equipment;
    (3) Hand-held motor-operated tools;
    (4) Motor-operated appliances of the following types: hedge 
clippers, lawn mowers, snow blowers, and wet scrubbers;
    (5) Cord- and plug-connected appliances used in damp or wet 
locations or by employees standing on the ground or on metal floors or 
working inside of metal tanks or boilers;
    (6) Portable and mobile X-ray and associated equipment;
    (7) Tools likely to be used in wet and conductive locations; and
    (8) Portable hand lamps.

Tools likely to be used in wet and conductive locations need not be 
grounded

[[Page 846]]

if supplied through an isolating transformer with an ungrounded 
secondary of not over 50 volts. Listed or labeled portable tools and 
appliances protected by an approved system of double insulation, or its 
equivalent, need not be grounded. If such a system is employed, the 
equipment shall be distinctively marked to indicate that the tool or 
appliance utilizes an approved system of double insulation.
    (vi) Nonelectrical equipment. The metal parts of the following 
nonelectrical equipment shall be grounded: frames and tracks of 
electrically operated cranes; frames of nonelectrically driven elevator 
cars to which electric conductors are attached; hand operated metal 
shifting ropes or cables of electric elevators, and metal partitions, 
grill work, and similar metal enclosures around equipment of over 750 
volts between conductors.
    (6) Methods of grounding fixed equipment. (i) Non-current-carrying 
metal parts of fixed equipment, if required to be grounded by this 
subpart, shall be grounded by an equipment grounding conductor which is 
contained within the same raceway, cable, or cord, or runs with or 
encloses the circuit conductors. For DC circuits only, the equipment 
grounding conductor may be run separately from the circuit conductors.
    (ii) Electric equipment is considered to be effectively grounded if 
it is secured to, and in electrical contact with, a metal rack or 
structure that is provided for its support and the metal rack or 
structure is grounded by the method specified for the non-current-
carrying metal parts of fixed equipment in paragraph (f)(6)(i) of this 
section. For installations made before April 16, 1981, only, electric 
equipment is also considered to be effectively grounded if it is secured 
to, and in metallic contact with, the grounded structural metal frame of 
a building. Metal car frames supported by metal hoisting cables attached 
to or running over metal sheaves or drums of grounded elevator machines 
are also considered to be effectively grounded.
    (7) Grounding of systems and circuits of 1000 volts and over (high 
voltage)--(i) General. If high voltage systems are grounded, they shall 
comply with all applicable provisions of paragraphs (f)(1) through 
(f)(6) of this section as supplemented and modified by this paragraph 
(f)(7).
    (ii) Grounding of systems supplying portable or mobile equipment. 
(See Sec.  1910.302(b)(3).) Systems supplying portable or mobile high 
voltage equipment, other than substations installed on a temporary 
basis, shall comply with the following:
    (A) Portable and mobile high voltage equipment shall be supplied 
from a system having its neutral grounded through an impedance. If a 
delta-connected high voltage system is used to supply the equipment, a 
system neutral shall be derived.
    (B) Exposed non-current-carrying metal parts of portable and mobile 
equipment shall be connected by an equipment grounding conductor to the 
point at which the system neutral impedance is grounded.
    (C) Ground-fault detection and relaying shall be provided to 
automatically de-energize any high voltage system component which has 
developed a ground fault. The continuity of the equipment grounding 
conductor shall be continuously monitored so as to de-energize 
automatically the high voltage feeder to the portable equipment upon 
loss of continuity of the equipment grounding conductor.
    (D) The grounding electrode to which the portable or mobile 
equipment system neutral impedance is connected shall be isolated from 
and separated in the ground by at least 20 feet from any other system or 
equipment grounding electrode, and there shall be no direct connection 
between the grounding electrodes, such as buried pipe, fence, etc.
    (iii) Grounding of equipment. All non-current-carrying metal parts 
of portable equipment and fixed equipment including their associated 
fences, housings, enclosures, and supporting structures shall be 
grounded. However, equipment which is guarded by location and isolated 
from ground need not be grounded. Additionally, pole-mounted 
distribution apparatus at a height exceeding 8 feet above ground or 
grade level need not be grounded.

[46 FR 4056, Jan. 16, 1981; 46 FR 40185, Aug. 7, 1981, as amended at 55 
FR 32015, Aug. 6, 1990]

[[Page 847]]


    Effective Date Note: At 72 FR 7195, 2007, Sec.  1910.304 was 
revised, effective Aug. 13, 2007. For the convenience of the user, the 
revised text is set forth as follows:

Sec.  1910.304  Wiring design and protection.

    (a) Use and identification of grounded and grounding conductors--(1) 
Identification of conductors. (i) A conductor used as a grounded 
conductor shall be identifiable and distinguishable from all other 
conductors.
    (ii) A conductor used as an equipment grounding conductor shall be 
identifiable and distinguishable from all other conductors.
    (2) Polarity of connections. No grounded conductor may be attached 
to any terminal or lead so as to reverse designated polarity.
    (3) Use of grounding terminals and devices. A grounding terminal or 
grounding-type device on a receptacle, cord connector, or attachment 
plug may not be used for purposes other than grounding.
    (b) Branch circuits--(1) Identification of multiwire branch 
circuits. Where more than one nominal voltage system exists in a 
building containing multiwire branch circuits, each ungrounded conductor 
of a multiwire branch circuit, where accessible, shall be identified by 
phase and system. The means of identification shall be permanently 
posted at each branch-circuit panelboard.
    (2) Receptacles and cord connectors. (i) Receptacles installed on 
15- and 20-ampere branch circuits shall be of the grounding type except 
as permitted for replacement receptacles in paragraph (b)(2)(iv) of this 
section. Grounding-type receptacles shall be installed only on circuits 
of the voltage class and current for which they are rated, except as 
provided in Table S-4 and Table S-5.
    (ii) Receptacles and cord connectors having grounding contacts shall 
have those contacts effectively grounded except for receptacles mounted 
on portable and vehicle-mounted generators in accordance with paragraph 
(g)(3) of this section and replacement receptacles installed in 
accordance with paragraph (b)(2)(iv) of this section.
    (iii) The grounding contacts of receptacles and cord connectors 
shall be grounded by connection to the equipment grounding conductor of 
the circuit supplying the receptacle or cord connector. The branch 
circuit wiring method shall include or provide an equipment grounding 
conductor to which the grounding contacts of the receptacle or cord 
connector shall be connected.
    (iv) Replacement of receptacles shall comply with the following 
requirements:
    (A) Where a grounding means exists in the receptacle enclosure or a 
grounding conductor is installed, grounding-type receptacles shall be 
used and shall be connected to the grounding means or conductor;
    (B) Ground-fault circuit-interrupter protected receptacles shall be 
provided where replacements are made at receptacle outlets that are 
required to be so protected elsewhere in this subpart; and
    (C) Where a grounding means does not exist in the receptacle 
enclosure, the installation shall comply with one of the following 
provisions:
    (1) A nongrounding-type receptacle may be replaced with another 
nongrounding-type receptacle; or
    (2) A nongrounding-type receptacle may be replaced with a ground-
fault circuit-interrupter-type of receptacle that is marked ``No 
Equipment Ground;'' an equipment grounding conductor may not be 
connected from the ground-fault circuit-interrupter-type receptacle to 
any outlet supplied from the ground-fault circuit-interrupter 
receptacle; or
    (3) A nongrounding-type receptacle may be replaced with a grounding-
type receptacle where supplied through a ground-fault circuit-
interrupter; the replacement receptacle shall be marked ``GFCI 
Protected'' and ``No Equipment Ground;'' an equipment grounding 
conductor may not be connected to such grounding-type receptacles.
    (v) Receptacles connected to circuits having different voltages, 
frequencies, or types of current (ac or dc) on the same premises shall 
be of such design that the attachment plugs used on these circuits are 
not interchangeable.
    (3) Ground-fault circuit interrupter protection for personnel. (i) 
All 125-volt, single-phase, 15- and 20-ampere receptacles installed in 
bathrooms or on rooftops shall have ground-fault circuit-interrupter 
protection for personnel.
    (ii) The following requirements apply to temporary wiring 
installations that are used during maintenance, remodeling, or repair of 
buildings, structures, or equipment or during similar construction-like 
activities.
    (A) All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle 
outlets that are not part of the permanent wiring of the building or 
structure and that are in use by personnel shall have ground-fault 
circuit-interrupter protection for personnel.

    Note 1 to paragraph (b)(3)(ii)(A) of this section: A cord connector 
on an extension cord set is considered to be a receptacle outlet if the 
cord set is used for temporary electric power.
    Note 2 to paragraph (b)(3)(ii)(A) of this section: Cord sets and 
devices incorporating the required ground-fault circuit-interrupter that 
are connected to the receptacle closest to the source of power are 
acceptable forms of protection.

    (B) Receptacles other than 125 volt, single-phase, 15-, 20-, and 30-
ampere receptacles that are not part of the permanent wiring of the 
building or structure and that are in use by personnel shall have 
ground-fault circuit-interrupter protection for personnel.

[[Page 848]]

    (C) Where the ground-fault circuit-interrupter protection required 
by paragraph (b)(3)(ii)(B) of this section is not available for 
receptacles other than 125-volt, single-phase, 15-, 20-, and 30-ampere, 
the employer shall establish and implement an assured equipment 
grounding conductor program covering cord sets, receptacles that are not 
a part of the building or structure, and equipment connected by cord and 
plug that are available for use or used by employees on those 
receptacles. This program shall comply with the following requirements:
    (1) A written description of the program, including the specific 
procedures adopted by the employer, shall be available at the jobsite 
for inspection and copying by the Assistant Secretary of Labor and any 
affected employee;
    (2) The employer shall designate one or more competent persons to 
implement the program;
    (3) Each cord set, attachment cap, plug, and receptacle of cord 
sets, and any equipment connected by cord and plug, except cord sets and 
receptacles which are fixed and not exposed to damage, shall be visually 
inspected before each day's use for external defects, such as deformed 
or missing pins or insulation damage, and for indications of possible 
internal damage. Equipment found damaged or defective shall not be used 
until repaired;
    (4) The following tests shall be performed on all cord sets and 
receptacles which are not a part of the permanent wiring of the building 
or structure, and cord- and plug-connected equipment required to be 
grounded:
    (i) All equipment grounding conductors shall be tested for 
continuity and shall be electrically continuous;
    (ii) Each receptacle and attachment cap or plug shall be tested for 
correct attachment of the equipment grounding conductor. The equipment 
grounding conductor shall be connected to its proper terminal; and
    (iii) All required tests shall be performed before first use; before 
equipment is returned to service following any repairs; before equipment 
is used after any incident which can be reasonably suspected to have 
caused damage (for example, when a cord set is run over); and at 
intervals not to exceed 3 months, except that cord sets and receptacles 
which are fixed and not exposed to damage shall be tested at intervals 
not exceeding 6 months;
    (5) The employer shall not make available or permit the use by 
employees of any equipment which has not met the requirements of 
paragraph (b)(3)(ii)(C) of this section; and
    (6) Tests performed as required in paragraph (b)(3)(ii)(C) of this 
section shall be recorded. This test record shall identify each 
receptacle, cord set, and cord- and plug-connected equipment that passed 
the test and shall indicate the last date it was tested or the interval 
for which it was tested. This record shall be kept by means of logs, 
color coding, or other effective means and shall be maintained until 
replaced by a more current record. The record shall be made available on 
the jobsite for inspection by the Assistant Secretary and any affected 
employee.
    (4) Outlet devices. Outlet devices shall have an ampere rating not 
less than the load to be served and shall comply with the following 
provisions:
    (i) Where connected to a branch circuit having a rating in excess of 
20 amperes, lampholders shall be of the heavy-duty type. A heavy-duty 
lampholder shall have a rating of not less than 660 watts if of the 
admedium type and not less than 750 watts if of any other type; and
    (ii) Receptacle outlets shall comply with the following provisions:
    (A) A single receptacle installed on an individual branch circuit 
shall have an ampere rating of not less than that of the branch circuit;
    (B) Where connected to a branch circuit supplying two or more 
receptacles or outlets, a receptacle may not supply a total cord- and 
plug-connected load in excess of the maximum specified in Table S-4; and
    (C) Where connected to a branch circuit supplying two or more 
receptacles or outlets, receptacle ratings shall conform to the values 
listed in Table S-5; or, where larger than 50 amperes, the receptacle 
rating may not be less than the branch-circuit rating. However, 
receptacles of cord- and plug-connected arc welders may have ampere 
ratings not less than the minimum branch-circuit conductor ampacity.
    (5) Cord connections. A receptacle outlet shall be installed 
wherever flexible cords with attachment plugs are used. Where flexible 
cords are permitted to be permanently connected, receptacles may be 
omitted.

     Table S-4--Maximum Cord- and Plug-Connected Load to Receptacle
------------------------------------------------------------------------
                                                 Receptacle    Maximum
           Circuit rating  (amperes)               rating        load
                                                 (amperes)    (amperes)
------------------------------------------------------------------------
15 or 20......................................           15           12
20............................................           20           16
30............................................           30           24
------------------------------------------------------------------------


         Table S-5--Receptacle Ratings for Various Size Circuits
------------------------------------------------------------------------
         Circuit rating  (amperes)          Receptacle rating  (amperes)
------------------------------------------------------------------------
15........................................  Not over 15.
20........................................  15 or 20.
30........................................  30.
40........................................  40 or 50.
50........................................  50.
------------------------------------------------------------------------


[[Page 849]]

    (c) Outside conductors, 600 volts, nominal, or less. The following 
requirements apply to branch-circuit, feeder, and service conductors 
rated 600 volts, nominal, or less and run outdoors as open conductors.
    (1) Conductors on poles. Conductors on poles shall have a separation 
of not less than 305 mm (1.0 ft) where not placed on racks or brackets. 
Conductors supported on poles shall provide a horizontal climbing space 
not less than the following:
    (i) Power conductors below communication conductors--762 mm (30 
in.);
    (ii) Power conductors alone or above communication conductors:
    (A) 300 volts or less--610 mm (24 in.),
    (B) Over 300 volts--762 mm (30 in.);
    (iii) Communication conductors below power conductors--same as power 
conductors; and
    (iv) Communications conductors alone--no requirement.
    (2) Clearance from ground. Open conductors, open multiconductor 
cables, and service-drop conductors of not over 600 volts, nominal, 
shall conform to the minimum clearances specified in Table S-6.

                                        Table S-6--Clearances From Ground
----------------------------------------------------------------------------------------------------------------
                                     Installations built before August 13,     Installations built on or after
                                                      2007                             August 13, 2007
              Distance              ----------------------------------------------------------------------------
                                                                                Voltage  to
                                       Maximum voltage       Conditions           ground           Conditions
----------------------------------------------------------------------------------------------------------------
3.05 m (10.0 ft)...................  < 600 V...........  Above finished     < 150 V...........  Above finished
                                                          grade or                               grade or
                                                          sidewalks, or                          sidewalks, or
                                                          from any                               from any
                                                          platform or                            platform or
                                                          projection from                        projection from
                                                          which they might                       which they
                                                          be reached. (If                        might be
                                                          these areas are                        reached. (If
                                                          accessible to                          these areas are
                                                          other than                             accessible to
                                                          pedestrian                             other than
                                                          traffic, then                          pedestrian
                                                          one of the other                       traffic, then
                                                          conditions                             one of the
                                                          applies).                              other
                                                                                                 conditions
                                                                                                 applies.)
3.66 m (12.0 ft)...................  < 600 V...........  Over areas, other  < 300 V...........  Over residential
                                                          than public                            property and
                                                          streets, alleys,                       driveways. Over
                                                          roads, and                             commercial
                                                          driveways,                             areas subject
                                                          subject to                             to pedestrian
                                                          vehicular                              traffic or to
                                                          traffic other                          vehicular
                                                          than truck                             traffic other
                                                          traffic.                               than truck
                                                                                                 traffic. (This
                                                                                                 category
                                                                                                 includes
                                                                                                 conditions
                                                                                                 covered under
                                                                                                 the 3.05-m
                                                                                                 (10.0-ft)
                                                                                                 category where
                                                                                                 the voltage
                                                                                                 exceeds 150 V.)
4.57 m (15.0 ft)...................  < 600 V...........  Over areas, other  301 to 600 V......  Over residential
                                                          than public                            property and
                                                          streets, alleys,                       driveways. Over
                                                          roads, and                             commercial
                                                          driveways,                             areas subject
                                                          subject to truck                       to pedestrian
                                                          traffic.                               traffic or to
                                                                                                 vehicular
                                                                                                 traffic other
                                                                                                 than truck
                                                                                                 traffic. (This
                                                                                                 category
                                                                                                 includes
                                                                                                 conditions
                                                                                                 covered under
                                                                                                 the 3.05-m
                                                                                                 (10.0-ft)
                                                                                                 category where
                                                                                                 the voltage
                                                                                                 exceeds 300 V.)
5.49 m (18.0 ft)...................  < 600 V...........  Over public        < 600 V...........  Over public
                                                          streets, alleys,                       streets,
                                                          roads, and                             alleys, roads,
                                                          driveways.                             and driveways.
                                                                                                 Over commercial
                                                                                                 areas subject
                                                                                                 to truck
                                                                                                 traffic. Other
                                                                                                 land traversed
                                                                                                 by vehicles,
                                                                                                 including land
                                                                                                 used for
                                                                                                 cultivating or
                                                                                                 grazing and
                                                                                                 forests and
                                                                                                 orchards.
----------------------------------------------------------------------------------------------------------------


[[Page 850]]

    (3) Clearance from building openings. (i) Service conductors 
installed as open conductors or multiconductor cable without an overall 
outer jacket shall have a clearance of not less than 914 mm (3.0 ft) 
from windows that are designed to be opened, doors, porches, balconies, 
ladders, stairs, fire escapes, and similar locations. However, 
conductors that run above the top level of a window may be less than 914 
mm (3.0 ft) from the window. Vertical clearance of final spans above, or 
within 914 mm (3.0 ft) measured horizontally of, platforms, projections, 
or surfaces from which they might be reached shall be maintained in 
accordance with paragraph (c)(2) of this section.
    (ii) Overhead service conductors may not be installed beneath 
openings through which materials may be moved, such as openings in farm 
and commercial buildings, and may not be installed where they will 
obstruct entrance to these building openings.
    (4) Above roofs. Overhead spans of open conductors and open 
multiconductor cables shall have a vertical clearance of not less than 
2.44 m (8.0 ft) above the roof surface. The vertical clearance above the 
roof level shall be maintained for a distance not less than 914 mm (3.0 
ft) in all directions from the edge of the roof.
    (i) The area above a roof surface subject to pedestrian or vehicular 
traffic shall have a vertical clearance from the roof surface in 
accordance with the clearance requirements of paragraph (c)(2) of this 
section.
    (ii) A reduction in clearance to 914 mm (3.0 ft) is permitted where 
the voltage between conductors does not exceed 300 and the roof has a 
slope of 102 mm (4 in.) in 305 mm (12 in.) or greater.
    (iii) A reduction in clearance above only the overhanging portion of 
the roof to not less than 457 mm (18 in.) is permitted where the voltage 
between conductors does not exceed 300 if:
    (A) The conductors do not pass above the roof overhang for a 
distance of more than 1.83 m (6.0 ft), 1.22 m (4.0 ft) horizontally, and
    (B) The conductors are terminated at a through-the-roof raceway or 
approved support.
    (iv) The requirement for maintaining a vertical clearance of 914 mm 
(3.0 ft) from the edge of the roof does not apply to the final conductor 
span, where the conductors are attached to the side of a building.
    (d) Location of outdoor lamps. Lamps for outdoor lighting shall be 
located below all energized conductors, transformers, or other electric 
equipment, unless such equipment is controlled by a disconnecting means 
that can be locked in the open position, or unless adequate clearances 
or other safeguards are provided for relamping operations.
    (e) Services--(1) Disconnecting means. (i) Means shall be provided 
to disconnect all conductors in a building or other structure from the 
service-entrance conductors. The service disconnecting means shall 
plainly indicate whether it is in the open or closed position and shall 
be installed at a readily accessible location nearest the point of 
entrance of the service-entrance conductors.
    (ii) Each service disconnecting means shall simultaneously 
disconnect all ungrounded conductors.
    (iii) Each service disconnecting means shall be suitable for the 
prevailing conditions.
    (2) Services over 600 volts, nominal. The following additional 
requirements apply to services over 600 volts, nominal.
    (i) Service-entrance conductors installed as open wires shall be 
guarded to make them accessible only to qualified persons.
    (ii) Signs warning of high voltage shall be posted where unqualified 
employees might come in contact with live parts.
    (f) Overcurrent protection--(1) 600 volts, nominal, or less. The 
following requirements apply to overcurrent protection of circuits rated 
600 volts, nominal, or less.
    (i) Conductors and equipment shall be protected from overcurrent in 
accordance with their ability to safely conduct current.
    (ii) Except for motor running overload protection, overcurrent 
devices may not interrupt the continuity of the grounded conductor 
unless all conductors of the circuit are opened simultaneously.
    (iii) A disconnecting means shall be provided on the supply side of 
all fuses in circuits over 150 volts to ground and cartridge fuses in 
circuits of any voltage where accessible to other than qualified persons 
so that each individual circuit containing fuses can be independently 
disconnected from the source of power. However, a current-limiting 
device without a disconnecting means is permitted on the supply side of 
the service disconnecting means. In addition, a single disconnecting 
means is permitted on the supply side of more than one set of fuses as 
permitted by the exception in Sec.  1910.305(j)(4)(vi) for group 
operation of motors, and a single disconnecting means is permitted for 
fixed electric space-heating equipment.
    (iv) Overcurrent devices shall be readily accessible to each 
employee or authorized building management personnel. These overcurrent 
devices may not be located where they will be exposed to physical damage 
or in the vicinity of easily ignitable material.
    (v) Fuses and circuit breakers shall be so located or shielded that 
employees will not be burned or otherwise injured by their operation. 
Handles or levers of circuit breakers, and similar parts that may move 
suddenly in such a way that persons in the vicinity are likely to be 
injured by being struck by them, shall be guarded or isolated.
    (vi) Circuit breakers shall clearly indicate whether they are in the 
open (off) or closed (on) position.

[[Page 851]]

    (vii) Where circuit breaker handles on switchboards are operated 
vertically rather than horizontally or rotationally, the up position of 
the handle shall be the closed (on) position.
    (viii) Circuit breakers used as switches in 120-volt and 277-volt, 
fluorescent lighting circuits shall be listed and marked ``SWD.''
    (ix) A circuit breaker with a straight voltage rating, such as 240 V 
or 480 V, may only be installed in a circuit in which the nominal 
voltage between any two conductors does not exceed the circuit breaker's 
voltage rating. A two-pole circuit breaker may not be used for 
protecting a 3-phase, corner-grounded delta circuit unless the circuit 
breaker is marked 1[Phi]--3[Phi] to indicate such suitability. A circuit 
breaker with a slash rating, such as 120/240 V or 480Y/277 V, may only 
be installed in a circuit where the nominal voltage of any conductor to 
ground does not exceed the lower of the two values of the circuit 
breaker's voltage rating and the nominal voltage between any two 
conductors does not exceed the higher value of the circuit breaker's 
voltage rating.
    (2) Feeders and branch circuits over 600 volts, nominal. The 
following requirements apply to feeders and branch circuits energized at 
more than 600 volts, nominal:
    (i) Feeder and branch-circuit conductors shall have overcurrent 
protection in each ungrounded conductor located at the point where the 
conductor receives its supply or at a location in the circuit determined 
under engineering supervision;
    (A) Circuit breakers used for overcurrent protection of three-phase 
circuits shall have a minimum of three overcurrent relays operated from 
three current transformers. On three-phase, three-wire circuits, an 
overcurrent relay in the residual circuit of the current transformers 
may replace one of the phase relays. An overcurrent relay, operated from 
a current transformer that links all phases of a three-phase, three-wire 
circuit, may replace the residual relay and one other phase-conductor 
current transformer. Where the neutral is not grounded on the load side 
of the circuit, the current transformer may link all three phase 
conductors and the grounded circuit conductor (neutral); and
    (B) If fuses are used for overcurrent protection, a fuse shall be 
connected in series with each ungrounded conductor;
    (ii) Each protective device shall be capable of detecting and 
interrupting all values of current that can occur at its location in 
excess of its trip setting or melting point;
    (iii) The operating time of the protective device, the available 
short-circuit current, and the conductor used shall be coordinated to 
prevent damaging or dangerous temperatures in conductors or conductor 
insulation under short-circuit conditions; and
    (iv) The following additional requirements apply to feeders only:
    (A) The continuous ampere rating of a fuse may not exceed three 
times the ampacity of the conductors. The long-time trip element setting 
of a breaker or the minimum trip setting of an electronically actuated 
fuse may not exceed six times the ampacity of the conductor. For fire 
pumps, conductors may be protected for short circuit only; and
    (B) Conductors tapped to a feeder may be protected by the feeder 
overcurrent device where that overcurrent device also protects the tap 
conductor.
    (g) Grounding. Paragraphs (g)(1) through (g)(9) of this section 
contain grounding requirements for systems, circuits, and equipment.
    (1) Systems to be grounded. Systems that supply premises wiring 
shall be grounded as follows:
    (i) All 3-wire dc systems shall have their neutral conductor 
grounded;
    (ii) Two-wire dc systems operating at over 50 volts through 300 
volts between conductors shall be grounded unless:
    (A) They supply only industrial equipment in limited areas and are 
equipped with a ground detector;
    (B) They are rectifier-derived from an ac system complying with 
paragraphs (g)(1)(iii), (g)(1)(iv), and (g)(1)(v) of this section; or
    (C) They are fire-alarm circuits having a maximum current of 0.030 
amperes;
    (iii) AC circuits of less than 50 volts shall be grounded if they 
are installed as overhead conductors outside of buildings or if they are 
supplied by transformers and the transformer primary supply system is 
ungrounded or exceeds 150 volts to ground;
    (iv) AC systems of 50 volts to 1000 volts shall be grounded under 
any of the following conditions, unless exempted by paragraph (g)(1)(v) 
of this section:
    (A) If the system can be so grounded that the maximum voltage to 
ground on the ungrounded conductors does not exceed 150 volts;
    (B) If the system is nominally rated three-phase, four-wire wye 
connected in which the neutral is used as a circuit conductor;
    (C) If the system is nominally rated three-phase, four-wire delta 
connected in which the midpoint of one phase is used as a circuit 
conductor; or
    (D) If a service conductor is uninsulated;
    (v) AC systems of 50 volts to 1000 volts are not required to be 
grounded under any of the following conditions:
    (A) If the system is used exclusively to supply industrial electric 
furnaces for melting, refining, tempering, and the like;
    (B) If the system is separately derived and is used exclusively for 
rectifiers supplying only adjustable speed industrial drives;
    (C) If the system is separately derived and is supplied by a 
transformer that has a primary voltage rating less than 1000 volts, 
provided all of the following conditions are met:

[[Page 852]]

    (1) The system is used exclusively for control circuits;
    (2) The conditions of maintenance and supervision ensure that only 
qualified persons will service the installation;
    (3) Continuity of control power is required; and
    (4) Ground detectors are installed on the control system;
    (D) If the system is an isolated power system that supplies circuits 
in health care facilities; or
    (E) If the system is a high-impedance grounded neutral system in 
which a grounding impedance, usually a resistor, limits the ground-fault 
current to a low value for 3-phase ac systems of 480 volts to 1000 volts 
provided all of the following conditions are met:
    (1) The conditions of maintenance and supervision ensure that only 
qualified persons will service the installation;
    (2) Continuity of power is required;
    (3) Ground detectors are installed on the system; and
    (4) Line-to-neutral loads are not served.
    (2) Conductor to be grounded. The conductor to be grounded for ac 
premises wiring systems required to be grounded by paragraph (g)(1) of 
this section shall be as follows:
    (i) One conductor of a single-phase, two-wire system shall be 
grounded;
    (ii) The neutral conductor of a single-phase, three-wire system 
shall be grounded;
    (iii) The common conductor of a multiphase system having one wire 
common to all phases shall be grounded;
    (iv) One phase conductor of a multiphase system where one phase is 
grounded shall be grounded; and
    (v) The neutral conductor of a multiphase system in which one phase 
is used as a neutral conductor shall be grounded.
    (3) Portable and vehicle-mounted generators. (i) The frame of a 
portable generator need not be grounded and may serve as the grounding 
electrode for a system supplied by the generator under the following 
conditions:
    (A) The generator supplies only equipment mounted on the generator 
or cord- and plug-connected equipment through receptacles mounted on the 
generator, or both; and
    (B) The noncurrent-carrying metal parts of equipment and the 
equipment grounding conductor terminals of the receptacles are bonded to 
the generator frame.
    (ii) The frame of a vehicle need not be grounded and may serve as 
the grounding electrode for a system supplied by a generator located on 
the vehicle under the following conditions:
    (A) The frame of the generator is bonded to the vehicle frame;
    (B) The generator supplies only equipment located on the vehicle and 
cord- and plug-connected equipment through receptacles mounted on the 
vehicle;
    (C) The noncurrent-carrying metal parts of equipment and the 
equipment grounding conductor terminals of the receptacles are bonded to 
the generator frame; and
    (D) The system complies with all other provisions of paragraph (g) 
of this section.
    (iii) A system conductor that is required to be grounded by the 
provisions of paragraph (g)(2) of this section shall be bonded to the 
generator frame where the generator is a component of a separately 
derived system.
    (4) Grounding connections. (i) For a grounded system, a grounding 
electrode conductor shall be used to connect both the equipment 
grounding conductor and the grounded circuit conductor to the grounding 
electrode. Both the equipment grounding conductor and the grounding 
electrode conductor shall be connected to the grounded circuit conductor 
on the supply side of the service disconnecting means or on the supply 
side of the system disconnecting means or overcurrent devices if the 
system is separately derived.
    (ii) For an ungrounded service-supplied system, the equipment 
grounding conductor shall be connected to the grounding electrode 
conductor at the service equipment. For an ungrounded separately derived 
system, the equipment grounding conductor shall be connected to the 
grounding electrode conductor at, or ahead of, the system disconnecting 
means or overcurrent devices.
    (iii) On extensions of existing branch circuits that do not have an 
equipment grounding conductor, grounding-type receptacles may be 
grounded to a grounded cold water pipe near the equipment if the 
extension was installed before August 13, 2007. When any element of this 
branch circuit is replaced, the entire branch circuit shall use an 
equipment grounding conductor that complies with all other provisions of 
paragraph (g) of this section.
    (5) Grounding path. The path to ground from circuits, equipment, and 
enclosures shall be permanent, continuous, and effective.
    (6) Supports, enclosures, and equipment to be grounded. (i) Metal 
cable trays, metal raceways, and metal enclosures for conductors shall 
be grounded, except that:
    (A) Metal enclosures such as sleeves that are used to protect cable 
assemblies from physical damage need not be grounded; and
    (B) Metal enclosures for conductors added to existing installations 
of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable need 
not be grounded if all of the following conditions are met:
    (1) Runs are less than 7.62 meters (25.0 ft);
    (2) Enclosures are free from probable contact with ground, grounded 
metal, metal laths, or other conductive materials; and

[[Page 853]]

    (3) Enclosures are guarded against employee contact.
    (ii) Metal enclosures for service equipment shall be grounded.
    (iii) Frames of electric ranges, wall-mounted ovens, counter-mounted 
cooking units, clothes dryers, and metal outlet or junction boxes that 
are part of the circuit for these appliances shall be grounded.
    (iv) Exposed noncurrent-carrying metal parts of fixed equipment that 
may become energized shall be grounded under any of the following 
conditions:
    (A) If within 2.44 m (8 ft) vertically or 1.52 m (5 ft) horizontally 
of ground or grounded metal objects and subject to employee contact;
    (B) If located in a wet or damp location and not isolated;
    (C) If in electrical contact with metal;
    (D) If in a hazardous (classified) location;
    (E) If supplied by a metal-clad, metal-sheathed, or grounded metal 
raceway wiring method; or
    (F) If equipment operates with any terminal at over 150 volts to 
ground.
    (v) Notwithstanding the provisions of paragraph (g)(6)(iv) of this 
section, exposed noncurrent-carrying metal parts of the following types 
of fixed equipment need not be grounded:
    (A) Enclosures for switches or circuit breakers used for other than 
service equipment and accessible to qualified persons only;
    (B) Electrically heated appliances that are permanently and 
effectively insulated from ground;
    (C) Distribution apparatus, such as transformer and capacitor cases, 
mounted on wooden poles, at a height exceeding 2.44 m (8.0 ft) above 
ground or grade level; and
    (D) Listed equipment protected by a system of double insulation, or 
its equivalent, and distinctively marked as such.
    (vi) Exposed noncurrent-carrying metal parts of cord- and plug-
connected equipment that may become energized shall be grounded under 
any of the following conditions:
    (A) If in hazardous (classified) locations (see Sec.  1910.307);
    (B) If operated at over 150 volts to ground, except for guarded 
motors and metal frames of electrically heated appliances if the 
appliance frames are permanently and effectively insulated from ground;
    (C) If the equipment is of the following types:
    (1) Refrigerators, freezers, and air conditioners;
    (2) Clothes-washing, clothes-drying, and dishwashing machines, sump 
pumps, and electric aquarium equipment;
    (3) Hand-held motor-operated tools, stationary and fixed motor-
operated tools, and light industrial motor-operated tools;
    (4) Motor-operated appliances of the following types: hedge 
clippers, lawn mowers, snow blowers, and wet scrubbers;
    (5) Cord- and plug-connected appliances used in damp or wet 
locations, or by employees standing on the ground or on metal floors or 
working inside of metal tanks or boilers;
    (6) Portable and mobile X-ray and associated equipment;
    (7) Tools likely to be used in wet and conductive locations; and
    (8) Portable hand lamps.
    (vii) Notwithstanding the provisions of paragraph (g)(6)(vi) of this 
section, the following equipment need not be grounded:
    (A) Tools likely to be used in wet and conductive locations if 
supplied through an isolating transformer with an ungrounded secondary 
of not over 50 volts; and
    (B) Listed or labeled portable tools and appliances if protected by 
an approved system of double insulation, or its equivalent, and 
distinctively marked.
    (7) Nonelectrical equipment. The metal parts of the following 
nonelectrical equipment shall be grounded: frames and tracks of 
electrically operated cranes and hoists; frames of nonelectrically 
driven elevator cars to which electric conductors are attached; hand-
operated metal shifting ropes or cables of electric elevators; and metal 
partitions, grill work, and similar metal enclosures around equipment of 
over 750 volts between conductors.
    (8) Methods of grounding fixed equipment. (i) Noncurrent-carrying 
metal parts of fixed equipment, if required to be grounded by this 
subpart, shall be grounded by an equipment grounding conductor that is 
contained within the same raceway, cable, or cord, or runs with or 
encloses the circuit conductors. For dc circuits only, the equipment 
grounding conductor may be run separately from the circuit conductors.
    (ii) Electric equipment is considered to be effectively grounded if 
it is secured to, and in electrical contact with, a metal rack or 
structure that is provided for its support and the metal rack or 
structure is grounded by the method specified for the noncurrent-
carrying metal parts of fixed equipment in paragraph (g)(8)(i) of this 
section. Metal car frames supported by metal hoisting cables attached to 
or running over metal sheaves or drums of grounded elevator machines are 
also considered to be effectively grounded.
    (iii) For installations made before April 16, 1981, electric 
equipment is also considered to be effectively grounded if it is secured 
to, and in metallic contact with, the grounded structural metal frame of 
a building. When any element of this branch circuit is replaced, the 
entire branch circuit shall use an equipment grounding conductor that 
complies with all other provisions of paragraph (g) of this section.

[[Page 854]]

    (9) Grounding of systems and circuits of 1000 volts and over (high 
voltage). If high voltage systems are grounded, they shall comply with 
all applicable provisions of paragraphs (g)(1) through (g)(8) of this 
section as supplemented and modified by the following requirements:
    (i) Systems supplying portable or mobile high voltage equipment, 
other than substations installed on a temporary basis, shall comply with 
the following:
    (A) The system shall have its neutral grounded through an impedance. 
If a delta-connected high voltage system is used to supply the 
equipment, a system neutral shall be derived.
    (B) Exposed noncurrent-carrying metal parts of portable and mobile 
equipment shall be connected by an equipment grounding conductor to the 
point at which the system neutral impedance is grounded.
    (C) Ground-fault detection and relaying shall be provided to 
automatically deenergize any high voltage system component that has 
developed a ground fault. The continuity of the equipment grounding 
conductor shall be continuously monitored so as to deenergize 
automatically the high voltage feeder to the portable equipment upon 
loss of continuity of the equipment grounding conductor.
    (D) The grounding electrode to which the portable equipment system 
neutral impedance is connected shall be isolated from and separated in 
the ground by at least 6.1 m (20.0 ft) from any other system or 
equipment grounding electrode, and there shall be no direct connection 
between the grounding electrodes, such as buried pipe, fence, and so 
forth.
    (ii) All noncurrent-carrying metal parts of portable equipment and 
fixed equipment, including their associated fences, housings, 
enclosures, and supporting structures, shall be grounded. However, 
equipment that is guarded by location and isolated from ground need not 
be grounded. Additionally, pole-mounted distribution apparatus at a 
height exceeding 2.44 m (8.0 ft) above ground or grade level need not be 
grounded.